![background image](http://html1.mh-extra.com/html/omega/sbr-ew100/sbr-ew100_user-manual_4033456049.webp)
4-8
IMSBR08-E2
• Resistance Temperature Detector (RTD)
Range Type
Parameter for
Range of Leftmost and
Range of Leftmost and
the SR Command
Rightmost Values of Span
Rightmost Values of Span
of the SR Command
Pt100
PT
–200.0 to 600.0
°
C
–2000 to 6000
JPt100
JPT
–200.0 to 550.0
°
C
–2000 to 5500
Difference between channels (DELTA)
Pt100
-
–800.0 to 800.0
°
C
–8000 to 8000
JPt100
-
–750.0 to 750.0
°
C
–7500 to 7500
• ON/OFF input (DI)
Range Type
Parameter for
Range of Leftmost and
Range of Leftmost and
the SR Command
Rightmost Values of Span
Rightmost Values of Span
of the SR Command
Level
LEVEL
0 to 1
†
0 to 1
Contact
CONT
0 to 1
††
0 to 1
†
“0” when less than 2.4 V, “1” when greater than or equal to 2.4 V.
††
“0” when contact is OFF, “1” when contact is ON.
Miscellaneous
Channel Number
• Pen model
Measurement channel: 01 to 04
Computation channel: 0A, 0B, 0C, 0D, 0E, 0F, 0G, 0J
• Dot model
Measurement channel:
SBR-EW100 : 01 to 06
SBR-EW180 : 01 to 24
Computation channel:
SBR-EW100 : 0A, 0B, 0C, 0D, 0E, 0F, 0G, 0J, 0K, 0M, 0N, 0P
SBR-EW180 : 0A, 0B, 0C, 0D, 0E, 0F, 0G, 0J, 0K, 0M, 0N, 0P,
1A, 1B, 1C, 1D, 1E, 1F, 1G, 1J, 1K, 1M, 1N, 1P
Relay Number (/A1, /A2, /A3, /A4, and /A5 Options)
• Models with the /A1 option: I01, I02
• Models with the /A2 option: I01 to I04
• Models with the /A3 option: I01 to I06
• Models with the /A4 option: I01 to I06, I11 to I16 (SBR-EW180)
• Models with the /A5 option: I01 to I06, I11 to I16, I21 to I26, I31 to I36 (SBR-EW180)
Communication Input Data
SBR-EW100
Pen model: C01 to C08, dot model: C01 to C12
SBR-EW180
Pen model: C01 to C08, dot model: C01 to C24
Computation Constant (/M1 option).
K01 to K30
Remote Control Input Terminal (/R1 Option)
D01 to D05
4.3 Parameter Values
Summary of Contents for SBR-EW100
Page 1: ...IMSBR08 E2 SBR EW100 EW180 Recorder Communication Interface User s Manual...
Page 2: ......
Page 99: ...3 2002...