4-28
IMSBR08-E2
• Be sure to set p2 and p3 so that p3 is greater than
or equal to p2.
• For the output flow of FIFO data, see appendix 4.
IS
Outputs status information.
Syntax
I S p 1
<terminator>
p 1
Output status information (0)
Example
Output status information.
I S 0
Description The output status can be masked using the status filter
(IF command).
FU
Outputs user information.
Syntax
F U p 1
<terminator>
p 1
Output user information (0)
Example
Output user information.
F U 0
Description Outputs the information of the user currently connected
to the recorder.
4.8 RS-422A/485
Dedicated Commands
ESC O Opens the instrument.
The ASCII code of ESC is 1BH.
Syntax
E S C O p 1
<terminator:CR+LF>
p 1
Instrument address (01 to 32)
Example
Open the instrument at address 01.
E S C O 0 1
Description • Specifies the address of the instrument with which
to communicate.
• Only one instrument can be opened at any given
time.
• When an instrument is opened with the ESC O
command, any other instrument that is currently
open is automatically closed.
• When this command is received correctly, the
recorder transmits the data “ESC 0 xx” (xx:
Instrument’s address).
• Use CR+LF for the terminator. LF cannot be used.
ESC C Closes the instrument.
The ASCII code of ESC is 1BH.
Syntax
E S C C p 1
<terminator:CR+LF>
p 1
Instrument address (01 to 32)
Example
Close the instrument at address 01.
E S C C 0 1
Description • Clears the current connection with the instrument.
• When this command is received correctly, the
recorder transmits the data “ESC C xx” (xx:
Instrument’s address).
• Use CR+LF for the terminator. LF cannot be used.
4.7 Output Commands/4.8 RS-422A/485 Dedicated Commands