![background image](http://html1.mh-extra.com/html/omega/sbr-ew100/sbr-ew100_user-manual_4033456058.webp)
4-17
IMSBR08-E2
Commands
4
Description Use the format below to specify the display ON/OFF
state of each channel.
• List the values one after another for all channels
and separate the measurement channels and
computation channels with a hyphen.
• Channels cannot be omitted.
• The characters after the hyphen are valid only on
models with the computation function (/M1 option).
For multiple display (display in which
different screens can be assigned to the
top and bottom sections
Syntax
V D
p1,p2,p3,p4,p5,p6,p7,p8,p9,p10,p11,p12
<terminator>
p 1
Screen number (01 to 15)
p 2
Display type
M u l t i p l e d i s p l a y
Display in which different screens can be
assigned to the top and bottom sections
p 3
Top section display type
1 C H d i g i t a l
1-channel digital display
2 C H d i g i t a l
2-channel digital display
3 C H d i g i t a l
3-channel digital display (SBR-EW180)
T I M E
Date/Time (SBR-EW100)
C h a r t s p e e d
Chart speed (SBR-EW100)
T I M E / C h a r t s p e e d
Date/Time/Chart speed (SBR-EW180)
C h a n n e l a l a r m s t a t u s
Channel alarm status display
S T A T U S
Status display
L i g h t o u t
Screen OFF
T a g _ 1 C H d i g i t a l
1-channel digital display (tag)
Note
Parameters that become invalid due to p3, p4, p8, or p9 setting
are skipped, and the next parameter is brought forward.
p 4
Displayed channel switching interval
Condition: Set this parameter when p3 is
1CH
d i g i t a l
or
2 C H d i g i t a l
.
M A N U A L
Fixed display channels, data
update rate (pen model): 2 s,
data update rate (dot model):
scan interval
A U T O 1 S
Switch the displayed channels
and data every 1 second.
A U T O 2 S
Switch the displayed channels
and data every 2 seconds.
A U T O 3 S
Switch the displayed channels
and data every 3 seconds.
A U T O 4 S
Switch the displayed channels
and data every 4 seconds.
A U T O 5 S
Switch the displayed channels
and data every 5 seconds.
p 5
Channel number
Condition: This parameter can be specified when
p3 is
1 C H d i g i t a l
,
2 C H
d i g i t a l
, or
T a g _ 1 C H d i g i t a l
and p4 is
M A N U A L
.
p 6
2nd channel number
Condition: This parameter is specified when p3 is
2 C H d i g i t a l
and p4 is
M A N U A L
.
p 7
3rd channel number
Condition: This parameter is specified when p3 is
3 C H d i g i t a l
and p4 is
M A N U A L
.
p 8
Bottom section display type
Same as p3
p 9
Displayed channel switching interval
Same as p4
p 1 0
Channel number
Same as p5
p 1 1
2nd channel number
Same as p6
p 1 2
3rd channel number
Same as p7
Query
V D [ p 1 ] ?
Example
Assign the display in which different screens can be
assigned to the top and bottom sections to screen 09.
Set the top section to status display and the bottom
section to 1-channel digital display. Switch the
displayed channel every 3 seconds (parameters p5 to
p7, p10, and p12 explained above are omitted).
V D 0 9 , M u l t i p l e
d i s p l a y , S T A T U S , 1 C H
d i g i t a l , A U T O 3 S
4.4 Setting Commands