3-5. Programming Over Current Protection(OCP)
Overcurrent protection guards the load against output currents that reach a specified value greater
than the programmed protection level. Below procedure is for setting the OCP level.
disable the OCP at the Factory Mode.
▌
Turn on the power supply
After turned on, check the power supply displays"**OUTPUT OFF**" Mode.
▌
Press the "Protection" key.
LCD Display
PROTECT> 1.OVP
▌
Press the right cursor key in order to enter the OCP.
LCD Display
PROTECT> 2.OCP
▌
Press the "Protection" key one more time at the "2. ocp" state.
LCD Display
OCP SET> 88.00a
▌
Move the under bar cursor location where you want to change
▌
Set the trip level
Note that you cannot set the trip levels to lower than current real output
Voltage in order to prevent the operator's malfunction occurring
▌
After set the limit levels that you want, press the "Protection" Key.
LCD Display
CHANGED
After displayed above message, The power supply will exit the OCP menu
and the display will return to the meter mode.
Cancelling
▌
If you don't want to change the OCP levels, just wait during 5 seconds.
Wait 5 sec
LCD Display
CANCEL…
≫ Related Remote Interface Command
CURR:OCP {<current>}
CURR:OCP?
CURR:OCP:TRIP?
CURR:OCP:CLE
apply: CURR:OCP 50
Set OCP Level
bout initial UVL setting, refer to Default Setting Values of "1-6. Check After Power On"
Note
- 33 -