Outputs
Inputs
Installation
3-12
P/N 7146386A
E
2008 Nordson Corporation
VBN w/o Control System
Interface Assignment
Interface Standard I/O
−
Standard Assignment for XS 2
−
General Information
S
To conform with a European standard regarding electro-magnetic
compatibility (EMC), only shielded cable may be connected. The shield
must
be connected to ground in compliance with the standard regarding
electromagnetic compatibility.
S
Inductive loads (e.g. solenoid valves) connected to the melter must be
equipped with a protective device (e.g. recovery diode) that disables the
inductive voltage generated when an inductive load is switched off.
S
The permitted voltage deviation is
10%.
Digital inputs
Pin
Input
Feature
1
*
24 V
DC
Internal (melter)
2
*
0 V
DC
External (customer’s)
NOTE:
Customer connects his reference potential here, if 24 V
DC
is provided by
customer.
10
Melter enable
11
Main contactor
12
Ready
13
Unit not ready
14
Fault indication
15
No fault indication
*
optional
Interfaces for Internal/External Pressure Sensors
The pressure sensors are connected to the terminal strip XLD. Refer to
wiring diagram.