Installation
3-6
P/N 7146386A
E
2008 Nordson Corporation
VBN w/o Control System
Electrical Connections
WARNING:
Risk of electrical shock. Failure to observe may result in
personal injury, death, or equipment damage.
Important Note When Using Residual Current Circuit Breakers
Local regulations in some industrial branches require residual current circuit
breakers.
Then observe the following points:
S
Residual current circuit breakers are to be installed only between the
power supply and the melter.
S
Use only residual current circuit breakers sensitive to pulsating current
or universal current (> 30 mA).
Laying Cable
WARNING:
Use only temperature resistant cable in warm areas of the
equipment. Ensure that cables do not touch rotating and/or hot melter
components. Do not pinch cables and check regularly for damage. Replace
damaged cables immediately!
Operating Voltage
WARNING:
Operate only at the operating voltage shown on the ID plate.
NOTE:
Permitted deviation from the rated line voltage is
10%.
NOTE:
The power cable cross-section must comply with the maximum
power consumption (refer to section
Technical Data).
External Control/Signal Circuits
WARNING:
Connect external control and signal circuits with suitable cable
in accordance with the NEC, class 1. To prevent short-circuiting, lay the
cables such that they do not touch printed circuits on PCBs.
Summary of Contents for VersaBlue 100H/100H
Page 46: ...Installation 3 14 P N 7146386A E 2008 Nordson Corporation VBN w o Control System...
Page 74: ...Maintenance 5 24 P N 7146386A E 2008 Nordson Corporation VBN w o Control System...
Page 94: ...Repair 7 14 P N 7146386A E 2008 Nordson Corporation VBN w o Control System...
Page 96: ...Parts 8 2 P N 7146386A E 2008 Nordson Corporation VBN w o Control System...