Calibrating
Prerequisites:
S
Level sensor is installed, fastened mechanically and connected
electrically (observe color coding of sensor cable)
S
Tank is empty (empty calibration: most sensitive setting, material
irrelevant)
S
Operating voltage is applied (LED
Operating voltage
(1) lit).
Sensor Break
1. Turn potentiometer
A
(3) 20 revolutions counterclockwise.
2. Turn potentiometer
P3
(2) counterclockwise until the green LED
empty
(5) is off and the red LED
full
(6) begins to flash.
3. Turn potentiometer
P3
counterclockwise to the switching point (green
LED
empty
on, red LED
full
off).
4. Then turn counterclockwise one or two more revolutions past the
switching point.
NOTE:
The closer the setting is to the switching point, the more precise is
the measurement. When the potentiometer
P3
is turned all the way
counterclockwise, sensor break monitoring is deactivated.
5. Perform function test: Disconnect sensor cable; sensor break monitoring
is triggered (red LED
full
flashes).
Fig. 7-15
Direction
Limit Switching Points
1. Turn potentiometer
A
clockwise to the switching point (green LED
empty
off, red LED
full
on).
2. Turn back from switching point until the green LED
empty
is on.
Summary of Contents for VersaBlue 100H/100H
Page 46: ...Installation 3 14 P N 7146386A E 2008 Nordson Corporation VBN w o Control System...
Page 74: ...Maintenance 5 24 P N 7146386A E 2008 Nordson Corporation VBN w o Control System...
Page 94: ...Repair 7 14 P N 7146386A E 2008 Nordson Corporation VBN w o Control System...
Page 96: ...Parts 8 2 P N 7146386A E 2008 Nordson Corporation VBN w o Control System...