background image

22

16 - WIRING AND CONNECTIONS

Permanent wiring is to be employed for the installation as required by 

local codes.

Use only U.L. listed (or equivalent) non-contact sensors. Inputs from the 
photo-beam to the circuit board are Normally Open (N.O.). Use only U.L. 
listed (or equivalent) non-contact sensors.
Connect the non-contact sensors. Inputs from the photo-beam to the circuit 
board are Normally Open (N.O.). Photo-beam input shall REVERSE travel 
of gate when activated during the CLOSE CYCLE ONLY. Gate will resume 
normal operation when photo-beam is no longer activated.
To reduce the risk of SEVERE INJURY or DEATH;
•  Disconnect power to the gate operator by manually opening its dedicated 

circuit breaker before making any mechanical or electrical adjustments.

•  Use a 20 Amp dedicated circuit breaker for each installed gate operator.
•  Open dedicated circuit breaker supplying power to this gate operator 

BEFORE a new installation or making any modifications to an existing 

installation of this gate operator.

•  All wiring connections MUST be made by a qualified individual.

•  Run individual circuits in separate U.L. listed conduits.  Do not combine 

high voltage (120VAC) power wiring and low voltage (+12VDC to +24VDC) 
control wiring in the same conduits.

•  It is highly recommended that a grounding rod be installed with each 

operator according to local building codes to provide protection against 
near lightning strikes.  Contact local underground utility companies 
BEFORE digging.

•  Use the information in Table 1 to determine high voltage wire size 

requirements. The distance shown in the chart is measured in feet from the 
operator to the power source. If power wiring is greater than the maximum 
distance shown, it is recommended that a service feeder be installed. 
When large gauge wire is used, a separate junction box must be installed 
for the operator connection. The wire table is based on stranded copper 
wire. Wire run calculations are based on a 110 VAC power source with a 
3% voltage drop on the power line, plus an additional 10% reduction in 
distance to allow for other losses in the system.

Table 1 - Wire Gauges and Maximum Power Circuit Distances

110V 

AWG 

14 12 

10 8 6 4

MAX RUN (ft) 

180 

280 

460 

700 

1150 

1800 

Figure 19 - GROUNDING WIRE

The gate operator  should  be  grounded to a copper rod  driven  to  a  
minimum  depth  of  3  feet, and properly grounded to the opener using a 
¼” copper wire  prior   to   operation.  Ensure proper ground bonding by 
removing paint around the mounting hole to create a proper connection if 
required. (Burnishing may be required) Check conductivity using a multimeter 

to verify bonding. (Ring-Out). See figure 19. 

  WARNING

This swing gate operator uses an inherent entrapment sensing system as well 
as external type sensors.

WARNING: External entrapment protection must be added to insure a 

safe vehicular gate operating system. 

Entrapment protection must be provided by a combination of non-contact 
inherent devices. Disconnect power to the gate operator before installing the 
non-contact sensors.
Actual placement of sensors is dependent on the specific installation 
requirements. 

One or more non-contact sensors should be located where the risk of 
entrapment or obstruction exists such as the perimeter reachable by a 
moving gate or barrier

ISOLATE ALL ELECTRICITY PRIOR TO INSTALLATION OR SERVICE

Deleting  All  Nice  Remote  Controls  from  the  Nice  Plug-In  Receiver 

Memory.

All programmed remote controls may be removed from the SMXI/A plug in 
receiver memory . This procedures need to be performed at the gate controller.

1.

 Press and hold the button on the side of the SMXI/A receiver until the led 

on the SMXI/A receiver illuminates green and keep the button pressed. 

2.

 Watch the led and on the receiver and verify the following sequence in the 

led.

3.

 Within 4 seconds after pressing the button (approx.) the green led 

illuminates.

4.

 Within 8 seconds after pressing the button (approx.) the green led turns off.

5.

 With 12 second after pressing the button (approx.) the green led starts 

flashing.

6.

 Count the green led flashes on the SMXI/A receiver. On 

EXACTLY the 5

TH 

flash, release the button on the SMXI/A receiver. 

7.

 It is recommended to test the FloR/A remote controls, if available, with 

SMXI/A plug in receiver to verify that it no longer affects the gate controller.

15 - ACCESSORY INPUTS AND OUTPUTS (CONT.)

16 - WIRING AND CONNECTIONS (CONT.)

Summary of Contents for Apollo 4300SW

Page 1: ...Revision 1 0 0_03 2012 Nice Apollo Swing Gate Opener Vehicular Swing Gate Opener 4300SW 1 2HP 4500SW 1HP...

Page 2: ......

Page 3: ...3 17 2 Fail safe connection 23 17 3 Magnetic lock connection 23 17 4 Guard station connection 23 17 5 Exit and edge inputs wiring diagram 24 17 6 Radio receiver connection third party 24 18 INSPECTION...

Page 4: ...tings need to be made A real time clock calendar enables programming for scheduled weekly or daily events like opening closing or locking the gate Gate opening and closing speed acceleration soft star...

Page 5: ...Drive Electromechanical Gate Length Max up to 16 ft 5 m up to 20 ft 6 m Gate Weight Max 600 lb leaf 272 kg 1 000 lb leaf 272 kg Open Close Time to 90 12 18s adjustable Temperature Rating 4 to 122 F 2...

Page 6: ...nd reliable operation it is essential these components operate together as a system It is the responsibility of the system designer and or installer to ensure any safety or operational issues have bee...

Page 7: ...le family dwellings 2 1 2 Class II Commercial General Access Gate Operator Intended for use in a commercial location or building such as a multi family housing units ve or more single family units hot...

Page 8: ...nt risk Swinging gates shall not open into public access areas 2 6 The gate must be properly installed and work freely in both directions prior to gate operator installation Don t change operator sett...

Page 9: ...vehicle detectors cannot provide protection to pedestrians In some situations photoelectric devices may be used as vehicle detectors but should be wired accordingly 4 Gate Construction and Safety Gate...

Page 10: ...slide gates 4 2 1 1 All weight bearing exposed rollers 8 ft 2 44 m or less above grade shall be guarded or covered 4 2 1 2 All openings shall be designed guarded or screened from the bottom of the ga...

Page 11: ...ll not be less than 16 in 406 mm Exception For a gate that is not in compliance with this provision the de ned area shall be subject to the entrapment protection provisions of UL 325 4 3 5 Class IV ve...

Page 12: ...aces is less than 16 in 406mm Potential entrapment zones are shown below for slide gates but keep in mind there may be other entrapment zones presented by the actual installation and adjacent structur...

Page 13: ...tion provided the gate in the open direction presents no risk of entrapment Slide Gates One sensor in the Open direction and one sensor in the Close direction The gate operator tests for the presence...

Page 14: ...ces s required Accessory Output Connections Power Input Connections Motor Output Connections BlueBus Connection Master Slave Connection Accessory Input Connections Earth Ground 9 4300 4500 PARTS IDENT...

Page 15: ...towed back for safe assembly of the gate operator Storage area for two 12VDC backup batteries for 24 volt motor power Use these holes for attaching I O cables with plastic zip ties Limit Switch 10 SWI...

Page 16: ...ical mounting Drill and insert RedHead 1 2 x 3 1 3 concrete anchors into the concrete sufficient to properly mount the gate opener Mounting position must be a minimum distance of 21 inches distance be...

Page 17: ...3 Steps 1 2 3 8 Adjust the Closed Limit Switch as done for the Open limit loosen the set screw and move the arm for the close limit until the RED light illuminates on the front of the control board se...

Page 18: ...on how to place the NICE 1050 control board into learning mode If the board is not in LEARN MODE press FUNCTION OK SWING OK LIGHT OK AVERAGE HEAVY You are in LEARN MODE if ENTER is flashing For dual...

Page 19: ...ttery is connected backwards a red LED will illuminate below the terminal Main DC Power This terminal block is for incoming 10 32VDC power only Connect wires to the main DC power terminal block Positi...

Page 20: ...and 3 pin and connector into the connection labeled Motor 2 for a dual leaf swing gate installation GREEN ORANGE BLUE YELLOW WHITE DO NOT USE RED BLACK MOTOR 1 4300 4500 ACTUATOR SINGLE MOTOR PULL TO...

Page 21: ...nstallation manual Limits and motor direction MUST be set prior to learning the board 2 Press and hold the OPEN or CLOSE button on the gate controller until the gate is 50 open 3 Press OK to allow the...

Page 22: ...AP Input 26 Dry contact input that can be programmed for an inductive safety loop or photo eye detector Shorting the ENTRAP input 26 to GND while the gate is opening cause the gate to close to the ful...

Page 23: ...specific control of individual gate functions The receiver includes built in programming functions for adding or removing Nice FloR A wireless remote controls to from a gate installation The followin...

Page 24: ...in the system Table 1 Wire Gauges and Maximum Power Circuit Distances 110V AWG 14 12 10 8 6 4 MAX RUN ft 180 280 460 700 1150 1800 Figure 19 GROUNDING WIRE The gate operator should be grounded to a c...

Page 25: ...arallel with the Fire input to release the motor in the event of an emergency entry by the fire department during a power failure Opening the FAIL SAFE contacts allows the gate to be pushed open by ha...

Page 26: ...f the correct type and amperage 18 9 Insufficient clearance between exposed current carrying parts and ground or poor insulation of exposed terminals All exposed connections must be covered prevent ar...

Page 27: ...xed object Figure 26 GENERAL GATE LAYOUT IN GROUND LOOPS Figure 26 GENERAL GATE LAYOUT WITH PHOTO EYES Possible Entrapment Zone Typical Installation Diagram Utilizing Loop Sensors and Photocells Possi...

Page 28: ...s a thru beam device consisting of a transmitter TX and a receiver RX that connects via two 2 wires Polarity of the wiring is not important EPMOBs may be wired in parallel to one another or directly t...

Page 29: ...ct Open Pule or Close Pulse and Press OK 5 Connect 300Hz Monitored Safety Device to In1 16 or NOTES Only one monitored Pulse device may be connected per input at In1 or In2 At least one monitored devi...

Page 30: ...ng Diagram EMX WEL 200 Wireless Edge Receiver Dip Switch Settings determine which relay activates when the associated edge is tripped See WEL 200 manual for instructions for programming receiver trans...

Page 31: ...R CHANGES ARE IMPLEMENTED TO ENSURE PROPER FUNCTIONALITY AND SAFETY 24 BOARD NOMENCLATURE Safety Shadow Entrap Shadow Adjust force settings for gate opening and closing Adjust speed settings for gate...

Page 32: ...ripherals enables the gate operator to discover and integrate accessory devices like Blue BUS access control and safety devices Positions Configures the points in the gate open close and partial cycle...

Page 33: ...ttery All the outputs are switched off and the LED OK blinks to show this standby status of the system Advance Settings The following settings are available for customizing the gate operator as requir...

Page 34: ...perator function except HIGH PRIORITY inputs COMMERCIAL GENERAL ACCESS VEHICULAR GATE OPERATOR CLASS II A vehicular gate operator or system intended for use in a commercial location or building such a...

Page 35: ...have accumulated Every 6 months 30 NICE GATE OPENER TROUBLESHOOTING POSSIBLE SOLUTION Check that power to the operator is turned ON Check terminal block wiring for loose or broken wires Check for 115...

Page 36: ...in each direction Appears when Swing gate operator does not have at least one entrapment sensor programmed and installed for both open and close direction for travel Appears when previously learned n...

Page 37: ...tance 48 std std 40 14 40 1 8 50 std std 37 14 42 1 8 51 1 2 std std 34 14 42 3 4 52 3 4 std std 31 14 42 3 4 54 std std 28 14 42 1 4 57 7 8 std std 13 14 37 1 2 Table 3 Installation layout E A B C D...

Page 38: ...33 TEMPLATE FOR INSTALLATION 3 Chart C A B C D E Ang 53 std std 24 3 4 16 100 53 13 16 std std 12 18 110 50 std std 11 22 120 Chart D A B C D E Distance 32 3 8 23 1 8 25 1 8 25 11 21 Table 4 21 Figure...

Page 39: ...37 34 COMPACT INSTALLATION ARM MEASUREMENTS Figure 32 ARM MEASUREMENTS 21 25 11 32 1 4 25 1 2 23 3 16 5 7 8 15 3 4 1 2 1 3 16 7 7 8 7 1 8 1 2 1 2 1 3 16 7 7 8 7 1 8 1 2 1 2...

Page 40: ...38 35 GATE ARM INSTALLATION Figure 33 CORRECT LAYOUT INCORRECT INSTALLATION Figure 34...

Page 41: ...er clockwise to release the adjustment knob 2 Rotate the knob as shown to increase or decrease the length of the main arm NOTE Do not extend the main arm more than 2 3 Using a 2 5mm or 3 32 hex key tu...

Page 42: ...ondition of the drive motor The gate will then run to the closing limit so that it can properly sense where it is located 13 The control board will then OPEN the gate slowly to establish travel and li...

Page 43: ...to make sure that the gate stops and reverses a short distance with minimal resistance applied Approximately 40 lbs on a swing gate at the end of the gate 8 The installer has instructed the customer i...

Page 44: ......

Page 45: ......

Page 46: ...Contact us Nice 6705 S 209th St Suite 101 Kent WA 98032 2327 Ph 1 253 867 3700 Fax 1 253 867 3702 www hysecurity com www facebook com hsgateoperators...

Reviews: