background image

8

4.1.5 

 An existing gate latch shall be disabled 

when a manually operated gate is retrofitted. 

4.1.6 

 A gate latch shall not be installed on an 

automatically operated gate.

4.1.7 

 Protrusions shall not be permitted on any 

gate. Consult ASTM F2200 for exceptions.

4.1.8 

 Gates shall be designed, constructed and 

installed such that their movement shall not 

be initiated by gravity when an automatic 

operator is disconnected.

4.1.9 

 For pedestrian access in the vicinity of 

an automated vehicular gate, a separate 

pedestrian gate shall be provided. The 

pedestrian gate shall be installed in a 

location such that a pedestrian shall not 

come in contact with a moving vehicular 

access gate. A pedestrian gate shall not be 

incorporated into an automated vehicular 

gate panel. 

4.1.10 

Any non-automated gate that is to 

be automated shall be upgraded to conform 

to the provisions of this specification.

4.1.11 

This specification shall not apply to 

gates generally used for pedestrian access 

and to vehicular gates not to be automated.

4.1.12 

Any existing automated gate, when 

the operator requires replacement, shall be 

upgraded to conform to the provisions of 

this specification in effect at that time.

4.2 

Vehicular Horizontal Slide Gate Requirements

4.2.1 

 The following provisions shall apply 

to Class I, Class II and Class III vehicular 

horizontal slide gates:

4.2.1.1 

All weight bearing exposed rollers 

8 ft (2.44 m), or less, above grade shall be 

guarded or covered

4.2.1.2 

All openings shall be designed, 

guarded, or screened from the bottom 

of the gate to the top of the gate or a 

minimum of 72 in. (1.83 m) above grade, 

whichever is less, to prevent a 2 1/4 in. (57 

mm) diameter sphere from passing through 

the openings anywhere in the gate, and in 

that portion of the adjacent fence that the 

gate covers in the open position. The gate 

panel shall include the entire section of the 

moving gate, including any back frame or 

counterbalance portion of the gate.

4.2.1.3 

A gap, measured in the horizontal 

plane parallel to the roadway, between 

a  fixed  stationary  object  nearest  the 

roadway (such as a gate support post) and 

the gate frame when the gate is in either 

the fully open position or the fully closed 

position, shall not exceed 2 1/4 in. (57 mm). 

Exception: All other fixed stationary objects 

greater than 16 in. (406 mm) from the gate 

frame shall not be required to comply with 

this section.

4.2.1.4 

Positive stops shall be required to 

limit travel to the designed fully open and 

fully closed positions. These stops shall 

be installed at either the top of the gate, 

or at the bottom of the gate where such 

stops shall horizontally or vertically project 

no more than is required to perform their 

intended function.

4.2.1.5 

All gates shall be designed with 

suffi cient lateral stability to assure that the 

gate will enter a receiver guide. Consult 

ASTM F2200 for details on various gate 

panel types.

Summary of Contents for Apollo 4300SW

Page 1: ...Revision 1 0 0_03 2012 Nice Apollo Swing Gate Opener Vehicular Swing Gate Opener 4300SW 1 2HP 4500SW 1HP...

Page 2: ......

Page 3: ...3 17 2 Fail safe connection 23 17 3 Magnetic lock connection 23 17 4 Guard station connection 23 17 5 Exit and edge inputs wiring diagram 24 17 6 Radio receiver connection third party 24 18 INSPECTION...

Page 4: ...tings need to be made A real time clock calendar enables programming for scheduled weekly or daily events like opening closing or locking the gate Gate opening and closing speed acceleration soft star...

Page 5: ...Drive Electromechanical Gate Length Max up to 16 ft 5 m up to 20 ft 6 m Gate Weight Max 600 lb leaf 272 kg 1 000 lb leaf 272 kg Open Close Time to 90 12 18s adjustable Temperature Rating 4 to 122 F 2...

Page 6: ...nd reliable operation it is essential these components operate together as a system It is the responsibility of the system designer and or installer to ensure any safety or operational issues have bee...

Page 7: ...le family dwellings 2 1 2 Class II Commercial General Access Gate Operator Intended for use in a commercial location or building such as a multi family housing units ve or more single family units hot...

Page 8: ...nt risk Swinging gates shall not open into public access areas 2 6 The gate must be properly installed and work freely in both directions prior to gate operator installation Don t change operator sett...

Page 9: ...vehicle detectors cannot provide protection to pedestrians In some situations photoelectric devices may be used as vehicle detectors but should be wired accordingly 4 Gate Construction and Safety Gate...

Page 10: ...slide gates 4 2 1 1 All weight bearing exposed rollers 8 ft 2 44 m or less above grade shall be guarded or covered 4 2 1 2 All openings shall be designed guarded or screened from the bottom of the ga...

Page 11: ...ll not be less than 16 in 406 mm Exception For a gate that is not in compliance with this provision the de ned area shall be subject to the entrapment protection provisions of UL 325 4 3 5 Class IV ve...

Page 12: ...aces is less than 16 in 406mm Potential entrapment zones are shown below for slide gates but keep in mind there may be other entrapment zones presented by the actual installation and adjacent structur...

Page 13: ...tion provided the gate in the open direction presents no risk of entrapment Slide Gates One sensor in the Open direction and one sensor in the Close direction The gate operator tests for the presence...

Page 14: ...ces s required Accessory Output Connections Power Input Connections Motor Output Connections BlueBus Connection Master Slave Connection Accessory Input Connections Earth Ground 9 4300 4500 PARTS IDENT...

Page 15: ...towed back for safe assembly of the gate operator Storage area for two 12VDC backup batteries for 24 volt motor power Use these holes for attaching I O cables with plastic zip ties Limit Switch 10 SWI...

Page 16: ...ical mounting Drill and insert RedHead 1 2 x 3 1 3 concrete anchors into the concrete sufficient to properly mount the gate opener Mounting position must be a minimum distance of 21 inches distance be...

Page 17: ...3 Steps 1 2 3 8 Adjust the Closed Limit Switch as done for the Open limit loosen the set screw and move the arm for the close limit until the RED light illuminates on the front of the control board se...

Page 18: ...on how to place the NICE 1050 control board into learning mode If the board is not in LEARN MODE press FUNCTION OK SWING OK LIGHT OK AVERAGE HEAVY You are in LEARN MODE if ENTER is flashing For dual...

Page 19: ...ttery is connected backwards a red LED will illuminate below the terminal Main DC Power This terminal block is for incoming 10 32VDC power only Connect wires to the main DC power terminal block Positi...

Page 20: ...and 3 pin and connector into the connection labeled Motor 2 for a dual leaf swing gate installation GREEN ORANGE BLUE YELLOW WHITE DO NOT USE RED BLACK MOTOR 1 4300 4500 ACTUATOR SINGLE MOTOR PULL TO...

Page 21: ...nstallation manual Limits and motor direction MUST be set prior to learning the board 2 Press and hold the OPEN or CLOSE button on the gate controller until the gate is 50 open 3 Press OK to allow the...

Page 22: ...AP Input 26 Dry contact input that can be programmed for an inductive safety loop or photo eye detector Shorting the ENTRAP input 26 to GND while the gate is opening cause the gate to close to the ful...

Page 23: ...specific control of individual gate functions The receiver includes built in programming functions for adding or removing Nice FloR A wireless remote controls to from a gate installation The followin...

Page 24: ...in the system Table 1 Wire Gauges and Maximum Power Circuit Distances 110V AWG 14 12 10 8 6 4 MAX RUN ft 180 280 460 700 1150 1800 Figure 19 GROUNDING WIRE The gate operator should be grounded to a c...

Page 25: ...arallel with the Fire input to release the motor in the event of an emergency entry by the fire department during a power failure Opening the FAIL SAFE contacts allows the gate to be pushed open by ha...

Page 26: ...f the correct type and amperage 18 9 Insufficient clearance between exposed current carrying parts and ground or poor insulation of exposed terminals All exposed connections must be covered prevent ar...

Page 27: ...xed object Figure 26 GENERAL GATE LAYOUT IN GROUND LOOPS Figure 26 GENERAL GATE LAYOUT WITH PHOTO EYES Possible Entrapment Zone Typical Installation Diagram Utilizing Loop Sensors and Photocells Possi...

Page 28: ...s a thru beam device consisting of a transmitter TX and a receiver RX that connects via two 2 wires Polarity of the wiring is not important EPMOBs may be wired in parallel to one another or directly t...

Page 29: ...ct Open Pule or Close Pulse and Press OK 5 Connect 300Hz Monitored Safety Device to In1 16 or NOTES Only one monitored Pulse device may be connected per input at In1 or In2 At least one monitored devi...

Page 30: ...ng Diagram EMX WEL 200 Wireless Edge Receiver Dip Switch Settings determine which relay activates when the associated edge is tripped See WEL 200 manual for instructions for programming receiver trans...

Page 31: ...R CHANGES ARE IMPLEMENTED TO ENSURE PROPER FUNCTIONALITY AND SAFETY 24 BOARD NOMENCLATURE Safety Shadow Entrap Shadow Adjust force settings for gate opening and closing Adjust speed settings for gate...

Page 32: ...ripherals enables the gate operator to discover and integrate accessory devices like Blue BUS access control and safety devices Positions Configures the points in the gate open close and partial cycle...

Page 33: ...ttery All the outputs are switched off and the LED OK blinks to show this standby status of the system Advance Settings The following settings are available for customizing the gate operator as requir...

Page 34: ...perator function except HIGH PRIORITY inputs COMMERCIAL GENERAL ACCESS VEHICULAR GATE OPERATOR CLASS II A vehicular gate operator or system intended for use in a commercial location or building such a...

Page 35: ...have accumulated Every 6 months 30 NICE GATE OPENER TROUBLESHOOTING POSSIBLE SOLUTION Check that power to the operator is turned ON Check terminal block wiring for loose or broken wires Check for 115...

Page 36: ...in each direction Appears when Swing gate operator does not have at least one entrapment sensor programmed and installed for both open and close direction for travel Appears when previously learned n...

Page 37: ...tance 48 std std 40 14 40 1 8 50 std std 37 14 42 1 8 51 1 2 std std 34 14 42 3 4 52 3 4 std std 31 14 42 3 4 54 std std 28 14 42 1 4 57 7 8 std std 13 14 37 1 2 Table 3 Installation layout E A B C D...

Page 38: ...33 TEMPLATE FOR INSTALLATION 3 Chart C A B C D E Ang 53 std std 24 3 4 16 100 53 13 16 std std 12 18 110 50 std std 11 22 120 Chart D A B C D E Distance 32 3 8 23 1 8 25 1 8 25 11 21 Table 4 21 Figure...

Page 39: ...37 34 COMPACT INSTALLATION ARM MEASUREMENTS Figure 32 ARM MEASUREMENTS 21 25 11 32 1 4 25 1 2 23 3 16 5 7 8 15 3 4 1 2 1 3 16 7 7 8 7 1 8 1 2 1 2 1 3 16 7 7 8 7 1 8 1 2 1 2...

Page 40: ...38 35 GATE ARM INSTALLATION Figure 33 CORRECT LAYOUT INCORRECT INSTALLATION Figure 34...

Page 41: ...er clockwise to release the adjustment knob 2 Rotate the knob as shown to increase or decrease the length of the main arm NOTE Do not extend the main arm more than 2 3 Using a 2 5mm or 3 32 hex key tu...

Page 42: ...ondition of the drive motor The gate will then run to the closing limit so that it can properly sense where it is located 13 The control board will then OPEN the gate slowly to establish travel and li...

Page 43: ...to make sure that the gate stops and reverses a short distance with minimal resistance applied Approximately 40 lbs on a swing gate at the end of the gate 8 The installer has instructed the customer i...

Page 44: ......

Page 45: ......

Page 46: ...Contact us Nice 6705 S 209th St Suite 101 Kent WA 98032 2327 Ph 1 253 867 3700 Fax 1 253 867 3702 www hysecurity com www facebook com hsgateoperators...

Reviews: