22
6.4.2
CONTROLLER TYPE
”
B
Ü
(PCGE 31 TO PCGE 520; OCGE 31 TO OCGE 240;
PCGEZ 37 TO PCGEZ 180)
The operating thermostat is supplied pre-adjusted according to the standard specifications of the chiller listed in the
supplement. The operating thermostat controls both the temperature regulating functions and the other safety pa-
rameters (e.g. alarm management and the running time of the electric motors). The complete list of parameters is
not supplied to the customer because changes in certain parameters may lead to problems affecting the reliability
and properties of the chiller.
Instructions for changing the parameters required by the user:
Changing the SET-POINT:
1.
Press the
key for 3 seconds (the set-point starts to flash).
2.
Use the
and
arrows to change the SETPOINT.
3.
Press the
key or wait 15 sec. (timeout), without pressing any key.
To access the
”
Pr1
’
user level:
1.
Press the
+
keys for a few seconds (the
and
LEDs start to flash) the upper display (red script)
shows
”
ALL
Ü
, which means the first group of parameters.
2.
Use the
and
arrows to scroll through the names of the parameter groups to be changed.
3.
After you have found the right parameter group, press the
key in order to enter and display all the pa-
rameters belonging to this group. The first parameter name appears on the display together with the value.
4.
Scroll through parameter list with the
and
arrows.
5.
Select the parameter you require.
6.
Press the
key to change its value.
7.
Change the value with the
and
keys.
8.
Press the
key again to confirm the new value. After a few seconds, the next parameter will be displayed.
To exit programming: press the
+
keys when a parameter is displayed or wait 15 sec. (timeout), without
pressing any key.
NOTE:
The new parameter value is also saved if the
keys are not pressed during the timeout.
CAUTION: It is only possible to change the value of the parameters (configuration parameters) when the chiller is
in standby mode.
While programming, press the
key in order to scroll through the parameter codes or increase the value.
List of parameters that can be changed with the procedure described:
Standard value
Code
Meaning
PCGE with
tank
PCGE*
without tank
OCG
E
PCGEZ
with tank
PCGEZ*
without tank
ST01
Set-point
15
20
25
-10
-5
ST02
Differential
3
3
3
3
3
Please contact the manufacturer for further parameters. (*probe set-point at inlet)
6.4.3
CONTROLLER TYPE
”
C
Ü
(PCGE 590 TO PCGE 3300; PCGEZ 240 TO PCGEZ 480)
The operating thermostat is supplied pre-adjusted according to the standard specifications of the chiller listed in the
supplement. The operating thermostat controls both the temperature regulating functions and the other safety pa-
rameters (e.g. alarm management and the running time of the electric motors). The complete list of parameters is
not supplied to the customer because changes in certain parameters may lead to problems affecting the reliability
and properties of the chiller.
Instructions for changing the parameters required by the user:
Summary of Contents for OCGE 111
Page 69: ...69 11 2 WIRING DIAGRAM MODELS PCGE 11 to PCGE 25 PCGEZ 08 230V 1Ph 50Hz POWER COMMAND DIAGRAM ...
Page 70: ...70 MODEL PCGE 28 230V 1Ph 50Hz POWER COMMAND DIAGRAM ...
Page 71: ...71 MODEL PCGE 28 400V 3Ph 50Hz POWER COMMAND DIAGRAM ...
Page 72: ...72 MODELS PCGE 31 to PCGE 41 OCGE 31 to OCGE 41 230V 1Ph 50Hz POWER SECTION ...
Page 73: ...73 MODELS PCGE 31 to PCGE 41 OCGE 31 to OCGE 41 230V 1Ph 50Hz COMMAND SECTION ...
Page 78: ...78 MODELS PCGE 590 to PCGE 3300 PCGEZ 360 to PCGEZ 480 400V 3Ph 50Hz ...
Page 79: ...79 ...
Page 80: ...80 ...
Page 81: ...81 ...
Page 86: ...86 MODEL PCGE 1100 with tank and pump MODEL PCGE 1300 with tank and pump ...
Page 87: ...87 MODEL PCGE 1900 2200 with tank and pump MODEL PCGE 2900 3300 with tank and pump ...
Page 91: ...91 MODEL PCGE 1100 without tank MODEL PCGE 1300 without tank ...
Page 92: ...92 MODEL PCGE 1900 2200 without tank MODEL PCGE 2900 3300 without tank ...
Page 97: ...97 710 1789 00 00 02B 轜 07 05 2008 ...
Page 166: ...69 11 2 WIRING DIAGRAM MODELS PCGE 11 to PCGE 25 PCGEZ 08 230V 1Ph 50Hz POWER COMMAND DIAGRAM ...
Page 167: ...70 MODEL PCGE 28 230V 1Ph 50Hz POWER COMMAND DIAGRAM ...
Page 168: ...71 MODEL PCGE 28 400V 3Ph 50Hz POWER COMMAND DIAGRAM ...
Page 169: ...72 MODELS PCGE 31 to PCGE 41 OCGE 31 to OCGE 41 230V 1Ph 50Hz POWER SECTION ...
Page 170: ...73 MODELS PCGE 31 to PCGE 41 OCGE 31 to OCGE 41 230V 1Ph 50Hz COMMAND SECTION ...
Page 175: ...78 MODELS PCGE 590 to PCGE 3300 PCGEZ 360 to PCGEZ 480 400V 3Ph 50Hz ...
Page 176: ...79 ...
Page 177: ...80 ...
Page 178: ...81 ...
Page 183: ...86 MODEL PCGE 1100 with tank and pump MODEL PCGE 1300 with tank and pump ...
Page 184: ...87 MODEL PCGE 1900 2200 with tank and pump MODEL PCGE 2900 3300 with tank and pump ...
Page 188: ...91 MODEL PCGE 1100 without tank MODEL PCGE 1300 without tank ...
Page 189: ...92 MODEL PCGE 1900 2200 without tank MODEL PCGE 2900 3300 without tank ...