Analog I/O Unit
FP0
4 - 4
Matsushita Automation Controls
4.1 Parts and Terminology
4.1.1
Analog Mode Switch Setting
Analog mode switch
Mode
Switch
number
Range
Analog
input
0 to 5V
0 to 20mA
-10 to +10V
K type thermocouple
(
*
Note 3)
J type thermocouple
(
*
Note 3)
T type thermocouple
(
*
Note 3)
input
range
switching
1 to 3, 5
No averag-
ing
(
*
Note 1)
With aver-
aging
(
*
Note 2)
No averag-
ing
(
*
Note 1)
With aver-
aging
(
*
Note 2)
Tempera-
ture of
terminal to
1000
q
C
-100
q
C to
tempera-
ture of
terminal
Tempera-
ture of
terminal to
750
q
C
-100
q
C to
tempera-
ture of
terminal
Tempera-
ture of
terminal to
350
q
C
-100
q
C to
tempera-
ture of
terminal
1
2
3
ON
5
Analog
output
4
0 to
20mA
-10 to
+10V
output
range
switching
ON
4
.
Notes
D
(
*
1): No averaging: Conversion data is set for the specified input
contact point area for each A/D conversion, on each channel.
D
(
*
2): With averaging: On each channel, for each A/D conversion,
the maximum and minimum values from the data of the
last ten times are excluded, and the data from the other
eight times is averaged, and the result set. (
*
section 4.7.1)
D
(
*
3): If a thermocouple setting is used, averaging is carried out,
regardless of the switch settings. (
*
section 4.7.2)
4.1.2
Analog I/O Terminal
Pin number
Name
Description
1
IN/V 0
Analog input (channel 0), voltage input
2
IN/I 0
Analog input (channel 0), current input
3
IN/COM
Analog input (channel 0 and 1), analog input
common
4
IN/V 1
Analog input (channel 1), voltage input
5
IN/I 1
Analog input (channel 1), current input
6
Ground for analog cable
7
OUT/V
Voltage output
8
OUT/I
Current output
9
OUT/COM
Analog output common
Summary of Contents for FP0 Series
Page 1: ...PROGRAMMABLE CONTROLLER FP0 Hardware is a global brand name of Matsushita Electric Works...
Page 12: ...Overview FP0 1 2 Matsushita Automation Controls...
Page 20: ...Overview FP0 1 10 Matsushita Automation Controls 1 4 Programming Tools...
Page 76: ...Analog I O Unit FP0 4 2 Matsushita Automation Controls...
Page 94: ...Analog I O Unit FP0 4 20 Matsushita Automation Controls 4 7 Averaging Function...
Page 96: ...I O Allocation FP0 5 2 Matsushita Automation Controls...
Page 102: ...Installation FP0 6 2 Matsushita Automation Controls...
Page 114: ...Wiring FP0 7 2 Matsushita Automation Controls...
Page 134: ...Wiring FP0 7 22 Matsushita Automation Controls 7 9 Wiring the RS232C Port...
Page 136: ...Connecting the I O P Display Panel FP0 8 2 Matsushita Automation Controls...
Page 141: ...Chapter 9 Trial Operation 9 1 Before Turning ON the Power 9 3 9 2 Turning the Power ON 9 4...
Page 142: ...Trial Operation FP0 9 2 Matsushita Automation Controls...
Page 146: ...Self Diagnostic and Troubleshooting FP0 10 2 Matsushita Automation Controls...
Page 160: ...Self Diagnostic and Troubleshooting FP0 10 16 Matsushita Automation Controls 10 3 Error Codes...
Page 162: ...Dimensions FP0 A 2 Matsushita Automation Controls...
Page 172: ...Record of changes FP0 R 2 Matsushita Automation Controls...