4.4 D/A Conversion Characteristics
4.4
D/A Conversion Characteristics
Digital input value
Output voltage (V)
-2000
-10.0
-1500
-7.5
-1000
-5.0
-500
-2.5
0
0.0
+500
+2.5
+1000
+5.0
+1500
+7.5
+2000
10.0
Processing if the range is exceeded
Digital input value
Analog output value
-2001 or less
Constant (value just before
-2001 is input)
+2001 or more
Constant (value just before
+2001 is input)
Digital input value
Output current (mA)
0
0.0
500
2.5
1000
5.0
1500
7.5
2000
10.0
2500
12.5
3000
15.0
3500
17.5
4000
20.0
Processing if the range is exceeded
Digital input value
Analog output value
Negative value
Constant (value just
before negative value is
input)
4001 or more
Constant (value just
before 4001 is input)
Voltage range: -10 to +10 V DC output
Correspondence table of D/A conversion
values
10
5
0
- 5
- 10
- 2000
- 1000
1000
2000(K)
(V)
Output
signal
range
Digital input
Correspondence table of D/A conversion
values
Current range: 0 to 20 mA output
15
10
5
0
(mA)
20
1000
2000
3000
4000 (K)
Output
signal
range
Digital input
Summary of Contents for FP0 Series
Page 1: ...PROGRAMMABLE CONTROLLER FP0 Hardware is a global brand name of Matsushita Electric Works...
Page 12: ...Overview FP0 1 2 Matsushita Automation Controls...
Page 20: ...Overview FP0 1 10 Matsushita Automation Controls 1 4 Programming Tools...
Page 76: ...Analog I O Unit FP0 4 2 Matsushita Automation Controls...
Page 94: ...Analog I O Unit FP0 4 20 Matsushita Automation Controls 4 7 Averaging Function...
Page 96: ...I O Allocation FP0 5 2 Matsushita Automation Controls...
Page 102: ...Installation FP0 6 2 Matsushita Automation Controls...
Page 114: ...Wiring FP0 7 2 Matsushita Automation Controls...
Page 134: ...Wiring FP0 7 22 Matsushita Automation Controls 7 9 Wiring the RS232C Port...
Page 136: ...Connecting the I O P Display Panel FP0 8 2 Matsushita Automation Controls...
Page 141: ...Chapter 9 Trial Operation 9 1 Before Turning ON the Power 9 3 9 2 Turning the Power ON 9 4...
Page 142: ...Trial Operation FP0 9 2 Matsushita Automation Controls...
Page 146: ...Self Diagnostic and Troubleshooting FP0 10 2 Matsushita Automation Controls...
Page 160: ...Self Diagnostic and Troubleshooting FP0 10 16 Matsushita Automation Controls 10 3 Error Codes...
Page 162: ...Dimensions FP0 A 2 Matsushita Automation Controls...
Page 172: ...Record of changes FP0 R 2 Matsushita Automation Controls...