Control Units
FP0
2 - 8
Matsushita Automation Controls
2.2 Specifications
2.2.1.2
Current Consumed by the Control Unit
The current consumed at the power supply connector of the control unit is the sum of
the current consumed by of the various units being used.
Type
Current consumption
(at 24 V DC)
Control unit
C10RS, C10CRS, C10RM, C10CRM
100 mA or less
C14RS, C14CRS, C14RM, C14CRM
100 mA or less
C16T, C16CT, C16P, C16CP
40 mA or less
C32T, C32CT, C32P, C32CP
60 mA or less
Expansion I/O
E8X
10 mA or less
p
/
unit
E8YT, E8YP
15 mA or less
E8RS, E8RM, E16RS, E16RM, E16X
20 mA or less
E16YT, E16YP, E16T, E16P
25 mA or less
E32T, E32P
40 mA or less
Analog I/O unit
A21
20 mA or less
FP Programmer
II
Ver. 2 (AFP1114V2)
50 mA or less
C-NET adapter S2 type (AFP15402)
50 mA or less
Current consumed when the unit requires an external power supply
With a relay output type of expansion I/O unit and an analog I/O unit, it is necessary to
provide a power supply to drive internal circuits.
Type
Current consumption
(at 24 V DC)
Expansion I/O
E8RS, E8RM
50 mA
p
/
unit
E16RS, E16RM
100 mA
Analog I/O unit
A21
100 mA
Summary of Contents for FP0 Series
Page 1: ...PROGRAMMABLE CONTROLLER FP0 Hardware is a global brand name of Matsushita Electric Works...
Page 12: ...Overview FP0 1 2 Matsushita Automation Controls...
Page 20: ...Overview FP0 1 10 Matsushita Automation Controls 1 4 Programming Tools...
Page 76: ...Analog I O Unit FP0 4 2 Matsushita Automation Controls...
Page 94: ...Analog I O Unit FP0 4 20 Matsushita Automation Controls 4 7 Averaging Function...
Page 96: ...I O Allocation FP0 5 2 Matsushita Automation Controls...
Page 102: ...Installation FP0 6 2 Matsushita Automation Controls...
Page 114: ...Wiring FP0 7 2 Matsushita Automation Controls...
Page 134: ...Wiring FP0 7 22 Matsushita Automation Controls 7 9 Wiring the RS232C Port...
Page 136: ...Connecting the I O P Display Panel FP0 8 2 Matsushita Automation Controls...
Page 141: ...Chapter 9 Trial Operation 9 1 Before Turning ON the Power 9 3 9 2 Turning the Power ON 9 4...
Page 142: ...Trial Operation FP0 9 2 Matsushita Automation Controls...
Page 146: ...Self Diagnostic and Troubleshooting FP0 10 2 Matsushita Automation Controls...
Page 160: ...Self Diagnostic and Troubleshooting FP0 10 16 Matsushita Automation Controls 10 3 Error Codes...
Page 162: ...Dimensions FP0 A 2 Matsushita Automation Controls...
Page 172: ...Record of changes FP0 R 2 Matsushita Automation Controls...