Wiring
FP0
7 - 7
Matsushita Automation Controls
7.3 Grounding
7.3
Grounding
Under normal conditions, the inherent noise resistance is sufficient. However, in
situations of excess noise, ground the instrument to increase noise suppression.
For grounding purposes, use wiring with a
minimum of 2 mm
2
. The grounding
connection should have a resistance of
less than 100
•
.
FP0
FP0
CORRECT
Other
device
Other
device
.
Notes
D
The point of grounding should be as close to the FP0 control
unit as possible. The ground wire should be as short as
possible.
D
If two devices share a single ground point, it may produce an
adverse effect. Always use an exclusive ground for each
device.
D
Depending on the surroundings in which the equipment is
used, grounding may cause problems.
<Example>
Since the power supply line (24 VDC and GND terminal) of the
FP0 power supply connector is connected to the frame ground
(F.G.) through a varistor, if there is an irregular potential
between the power supply line (24 VDC and GND) and earth,
the varistor may be shorted.
24 V DC
GND
F.G.
Varistor
Varistor (39 V DC)
Power supply lines
Power supply connector
of FP0 control unit
®
¯
Summary of Contents for FP0 Series
Page 1: ...PROGRAMMABLE CONTROLLER FP0 Hardware is a global brand name of Matsushita Electric Works...
Page 12: ...Overview FP0 1 2 Matsushita Automation Controls...
Page 20: ...Overview FP0 1 10 Matsushita Automation Controls 1 4 Programming Tools...
Page 76: ...Analog I O Unit FP0 4 2 Matsushita Automation Controls...
Page 94: ...Analog I O Unit FP0 4 20 Matsushita Automation Controls 4 7 Averaging Function...
Page 96: ...I O Allocation FP0 5 2 Matsushita Automation Controls...
Page 102: ...Installation FP0 6 2 Matsushita Automation Controls...
Page 114: ...Wiring FP0 7 2 Matsushita Automation Controls...
Page 134: ...Wiring FP0 7 22 Matsushita Automation Controls 7 9 Wiring the RS232C Port...
Page 136: ...Connecting the I O P Display Panel FP0 8 2 Matsushita Automation Controls...
Page 141: ...Chapter 9 Trial Operation 9 1 Before Turning ON the Power 9 3 9 2 Turning the Power ON 9 4...
Page 142: ...Trial Operation FP0 9 2 Matsushita Automation Controls...
Page 146: ...Self Diagnostic and Troubleshooting FP0 10 2 Matsushita Automation Controls...
Page 160: ...Self Diagnostic and Troubleshooting FP0 10 16 Matsushita Automation Controls 10 3 Error Codes...
Page 162: ...Dimensions FP0 A 2 Matsushita Automation Controls...
Page 172: ...Record of changes FP0 R 2 Matsushita Automation Controls...