Analog I/O Unit
FP0
4 - 8
Matsushita Automation Controls
4.2 Specifications
4.2.3
Analog Output Specifications
Item
Description
Number of output points
1 channel/unit
Output range
Voltage range
-10 to +10 V
p
g
Current range
0 to 20 mA
Digital input
-10 to +10 V
K - 2000 to K + 2000 (HF830 to H07D0)
g
p
0 to 20 mA
K0 to K4000 (H0 to H0FA0)
Resolution
1/4000
Conversion speed
500
μ
s (
*
Note 1)
Overall precision
1% F.S. or less (0 to 55
q
C/32 to 131
q
F)
0.6% F.S. or less (25
q
C/77
q
F)
Output
impedence
Voltage range
0.5
Ω
Maximum output
current
Voltage range
10 mA
Allowable output
load resistance
Current range
300
Ω
or less
Insulation method (
*
Note 2)
Between analog output terminal to FP0 internal circuit:
Photocoupler insulation
Between analog output terminal to analog I/O unit external power supply:
insulation-type DC/DC converter
Between analog output terminal to analog input terminal:
insulation-type DC/DC converter
Number of output contact points
16 output contact points: analog output data (WY2) (
*
Note 3)
.
Notes
D
(
*
1): The time noted below is required before the analog data is
reflected in the control unit output.
Waiting for
processing
1 ms
×
number of
expansion units
10V
K0
K2000
0 ms to
scan time
Analog output
WY2
0V
Refresh
Conversion time
(500
μ
s)
D
(
*
2): Refer to the schematic diagram of insulation methods on
the previous page.
D
(
*
3): The number for the output contact point being used varies
depending on the expansion location (
*
section 5.4).
Summary of Contents for FP0 Series
Page 1: ...PROGRAMMABLE CONTROLLER FP0 Hardware is a global brand name of Matsushita Electric Works...
Page 12: ...Overview FP0 1 2 Matsushita Automation Controls...
Page 20: ...Overview FP0 1 10 Matsushita Automation Controls 1 4 Programming Tools...
Page 76: ...Analog I O Unit FP0 4 2 Matsushita Automation Controls...
Page 94: ...Analog I O Unit FP0 4 20 Matsushita Automation Controls 4 7 Averaging Function...
Page 96: ...I O Allocation FP0 5 2 Matsushita Automation Controls...
Page 102: ...Installation FP0 6 2 Matsushita Automation Controls...
Page 114: ...Wiring FP0 7 2 Matsushita Automation Controls...
Page 134: ...Wiring FP0 7 22 Matsushita Automation Controls 7 9 Wiring the RS232C Port...
Page 136: ...Connecting the I O P Display Panel FP0 8 2 Matsushita Automation Controls...
Page 141: ...Chapter 9 Trial Operation 9 1 Before Turning ON the Power 9 3 9 2 Turning the Power ON 9 4...
Page 142: ...Trial Operation FP0 9 2 Matsushita Automation Controls...
Page 146: ...Self Diagnostic and Troubleshooting FP0 10 2 Matsushita Automation Controls...
Page 160: ...Self Diagnostic and Troubleshooting FP0 10 16 Matsushita Automation Controls 10 3 Error Codes...
Page 162: ...Dimensions FP0 A 2 Matsushita Automation Controls...
Page 172: ...Record of changes FP0 R 2 Matsushita Automation Controls...