Wiring
FP0
7 - 9
Matsushita Automation Controls
7.4 Input Wiring
7.4.2
LED-Equipped Reed Switch
When a LED is connected to an input contact such as LED-equipped reed switch, make
sure that the ON voltage applied to the FP0 input circuit is greater than 19.2 V DC.
In particular, take care when connecting a number of switches in series.
FP0
19.2 V DC
or more
24 V DC
LED-equipped
reed switch
COM
Input
terminal
7.4.3
Two-Wire Type Sensor
If the input of the FP0 does not turn OFF because of leakage current from the two-wire
type sensor, the use of a bleeder resistor is recommended, as shown below.
The OFF voltage of the FP0 input is 2.4 V, therefore, select an R value so that the voltage
between the COM terminal and the input terminal will be less than 2.4 V.
(The impedance of the FP0 input terminal is 5.6 k
:
.)
The resistance R of the bleeder resistor is: R
≦
The wattage W of the resistor is:
In the actual selection, use a value that is 3 to 5 times the value of W.
13.44
(Power supply voltage)
2
R
(k
:
)
Two-wire
type sensor
FP0
5.6
×
I
2.4
W
=
COM
Input terminal
Internal
circuit
Bleeder
resistor
I
: Sensor’s leakage current (mA)
R: Bleeder resistor (k
Ω
)
Summary of Contents for FP0 Series
Page 1: ...PROGRAMMABLE CONTROLLER FP0 Hardware is a global brand name of Matsushita Electric Works...
Page 12: ...Overview FP0 1 2 Matsushita Automation Controls...
Page 20: ...Overview FP0 1 10 Matsushita Automation Controls 1 4 Programming Tools...
Page 76: ...Analog I O Unit FP0 4 2 Matsushita Automation Controls...
Page 94: ...Analog I O Unit FP0 4 20 Matsushita Automation Controls 4 7 Averaging Function...
Page 96: ...I O Allocation FP0 5 2 Matsushita Automation Controls...
Page 102: ...Installation FP0 6 2 Matsushita Automation Controls...
Page 114: ...Wiring FP0 7 2 Matsushita Automation Controls...
Page 134: ...Wiring FP0 7 22 Matsushita Automation Controls 7 9 Wiring the RS232C Port...
Page 136: ...Connecting the I O P Display Panel FP0 8 2 Matsushita Automation Controls...
Page 141: ...Chapter 9 Trial Operation 9 1 Before Turning ON the Power 9 3 9 2 Turning the Power ON 9 4...
Page 142: ...Trial Operation FP0 9 2 Matsushita Automation Controls...
Page 146: ...Self Diagnostic and Troubleshooting FP0 10 2 Matsushita Automation Controls...
Page 160: ...Self Diagnostic and Troubleshooting FP0 10 16 Matsushita Automation Controls 10 3 Error Codes...
Page 162: ...Dimensions FP0 A 2 Matsushita Automation Controls...
Page 172: ...Record of changes FP0 R 2 Matsushita Automation Controls...