Control Units
FP0
2 - 10
Matsushita Automation Controls
2.2 Specifications
2.2.2
Performance Specifications
Item
Relay output type
Transistor output
type
Item
C10RS/C10CRS
C10RM/C10CRM
C14RS/C14CRS
C14RM/C14CRM
C16T/C16CT
C16P/C16CP
C32T/C32CT
C32P/C32CP
Programming method/Control method
Relay symbol/Cyclic operation
Controllable I/O
points
Control unit
only
total: 10
Input: 6
Output: 4
total: 14
Input: 8
Output: 6
total: 16
Input: 8
Output: 8
total: 32
Input: 16
Output: 16
When the
expansion unit
is the same
output type as
the control unit
max. 58
max. 62
max. 112
max. 128
When the
expansion unit
is a transistor
output type
max. 106
max. 110
max. 112
max. 128
Program memory
Built in EEPROM (no back-up battery required)
Program capacity
2,720 steps
5,000
steps
Numbers of
instruction
Basic
instruction
83 types
st uct o
High-level
instruction
114 types
Operation speed
0.9
μ
s/step (basic instruction)
I/O update time and Base time
Without expansion: 0.3 ms
With expansion: 0.3 ms + (1
×
Number of
expansion unit) ms
O
ti
R l
I t
l l
(R)
1 008
i
(R0
R62F)
Operation Relays
Internal relay (R)
1 008 points (R0 to R62F)
Operation Relays
Internal relay (R)
1,008 points (R0 to R62F)
Operation
memory
points
Relays
Special internal
relay (R)
64 points (R9000 to R903F)
Timer/Counter
(T/C)
144 points (initial setting is 100 timer points, T0 to
T99 / 44 counter points, C100 to C143 (
*
Note)
Timer range: 1 ms, 10 ms, 100 ms, 1 s; selected by
instruction
.
Note
The proportion of timer points to counter points can be changed
using a system register 5. See the
*
FP0 Programming Manual.
Summary of Contents for FP0 Series
Page 1: ...PROGRAMMABLE CONTROLLER FP0 Hardware is a global brand name of Matsushita Electric Works...
Page 12: ...Overview FP0 1 2 Matsushita Automation Controls...
Page 20: ...Overview FP0 1 10 Matsushita Automation Controls 1 4 Programming Tools...
Page 76: ...Analog I O Unit FP0 4 2 Matsushita Automation Controls...
Page 94: ...Analog I O Unit FP0 4 20 Matsushita Automation Controls 4 7 Averaging Function...
Page 96: ...I O Allocation FP0 5 2 Matsushita Automation Controls...
Page 102: ...Installation FP0 6 2 Matsushita Automation Controls...
Page 114: ...Wiring FP0 7 2 Matsushita Automation Controls...
Page 134: ...Wiring FP0 7 22 Matsushita Automation Controls 7 9 Wiring the RS232C Port...
Page 136: ...Connecting the I O P Display Panel FP0 8 2 Matsushita Automation Controls...
Page 141: ...Chapter 9 Trial Operation 9 1 Before Turning ON the Power 9 3 9 2 Turning the Power ON 9 4...
Page 142: ...Trial Operation FP0 9 2 Matsushita Automation Controls...
Page 146: ...Self Diagnostic and Troubleshooting FP0 10 2 Matsushita Automation Controls...
Page 160: ...Self Diagnostic and Troubleshooting FP0 10 16 Matsushita Automation Controls 10 3 Error Codes...
Page 162: ...Dimensions FP0 A 2 Matsushita Automation Controls...
Page 172: ...Record of changes FP0 R 2 Matsushita Automation Controls...