365 – AL Stop SV Wiring Ground
ZKP-Number: 1.8004.561
Injector wiring faulty
Red alarm – engine shutdown via protection module possible
Cause
Corrective action
Short circuit of injector positive
connection to ground of one or
more injectors.
Short circuit of the negative
injector connection or of one or
more injectors to ground.
1. Check wiring (→ Page 189).
2. Restart engine (→ Page 29).
381 – AL Wiring TOP 1
ZKP-Number: 2.8006.638
Line disruption on digital input 1
Yellow alarm – warning
Cause
Corrective action
Short circuit or wire break on
transistor output 1, plant side
(TOP 1).
u
Check wiring to plant.
382 – AL Wiring TOP 2
ZKP-Number: 2.8006.639
Line disruption on digital input 2
Yellow alarm – warning
Cause
Corrective action
Short circuit or wire break on
transistor output 2, plant side
(TOP 2).
u
Check wiring to plant.
383 – AL Wiring TOP 3
ZKP-Number: 2.8006.640
Line disruption on digital input 3
Yellow alarm – warning
Cause
Corrective action
Short circuit or wire break on
transistor output 3, plant side 3
(TOP 3).
u
Check wiring to plant.
MS150112/01E 2014-10
| Troubleshooting | 69