95 – AL Priming Fault
ZKP-Number: 2.1090.920
Oil priming fault.
Yellow alarm – warning
Cause
Corrective action
Priming oil pressure not
reached.
1. Check priming system.
2. Contact Service.
102 – AL Fuel Cons. Counter Defect
ZKP-Number: 1.8004.624
Fault in fuel checksum
Yellow alarm – warning
Cause
Corrective action
Consumption meter faulty.
u
Contact Service.
104 – AL Eng Hours Counter Defect
ZKP-Number: 1.8004.623
Fault in operating hours monitoring system
Yellow alarm – warning
Cause
Corrective action
Hour meter faulty.
u
Contact Service.
118 – LO ECU Supply Voltage
ZKP-Number: 2.0140.921
Supply voltage too low (limit value 1)
Yellow alarm – warning
Cause
Corrective action
Supply voltage at engine
governor too low.
1. Check engine governor supply voltage.
2. Contact Service.
119 – LOLO ECU Supply Voltage
ZKP-Number: 2.0140.922
Supply voltage too low (limit value 2)
Red alarm – start terminated
Cause
Corrective action
Supply voltage at engine
governor too low.
1. Check engine governor supply voltage.
2. Contact Service.