ioLogik W5300
Click&Go Logic
4-21
Expansion Module Connection Fail
The slot you select in the
Expansion Module Connection Fail
window will monitor while Click&Go is running. The monitored
target is specified for these expansion modules.
System Start-up
Click&Go logic provides the IF condition to perform an action,
such as triggering the local output or SMS alarm to indicate
that the system is restarting.
More Information about Repeat Interval vs. Edge Detection
Combining the Timer function with other IF conditions allows actions to be repeated when the specified logic is
sustained over a period of time. However, if a condition is based on edge detection (i.e.,
ON to OFF
or
OFF to
ON
), it can only be triggered once.
The following scenarios illustrate how edge detection affects the
Timer = N sec
. In each diagram, the statuses
of three sensors are shown over a period of time, with a high signal corresponding to a “true” condition. The
green shaded area shows the duration of time that the IF conditions have been met.
No Edge Detection
In this scenario, the rule checks each sensor for “on” status, so edge detection is not involved. As long as the
sensors remain on, the required conditions are satisfied, and the THEN actions will repeat at interval N.
DI-0 = ON
DI-1 = ON
DI-2 = ON
Relation between
conditions
AND
OR
“IF” conditions
satisfied
Repeat interval
“Timer = N sec”
“Timer = N sec”
“THEN” action
triggered