ioLogik W5300
Click&Go Logic
4-17
Under
Relation between conditions
, select
AND
to specify that all conditions must be satisfied for the
actions to take place; select
OR
to specify that any one of the conditions can be satisfied for the actions to take
place. The
Equivalent Logic Statement
at the bottom shows a real-time text-based summary of the rule that
you are defining. It provides a useful way to make sure the rule is designed as you intended.
IF…THEN/ELSE Conditionals
IF
statements are trigger
THEN/ELSE actions
. Under the
IF
column, you can set up to 3 conditions that must
be satisfied (when more than one condition is defined,
AND
or
OR
determinants are used to complete the logic),
and which will, according to the inputs, determine whether actions under the
THEN
or
ELSE
column will take
effect. For example, an alarm can be activated when a door is opened. Use the pull downs to specify the
conditions and units of measurement (e.g., DI-0=OFF).
IF conditions may be defined as follows:
IF Conditions
Operators
Remark
DI
ON, OFF, ON to OFF, OFF to ON, Change
DI-x represents the channel number
Counter
=, >, <, >=, <=, Change
Counter-x represents the channel number.
Max Counter Value: 4,294,967,295
AI
=, >, <, >=, <=
AI-x represents the number of the channel.
Max Value: Depends on the analog modes
or the result of scaling. Internal
Register(Float) can be used as the
comparison or throughput setting
controlled by remote SCADA or a
Modbus/TCP program.
Relay
=, >, <, >=, <=
CurRelayCNT-x represents the current relay
counts for the channel.
Max Value: 4,294,967,295
Internal Register =
Reg-x represents the number of the internal
register.
x = 00 to 23 / Trigger Value: 0 to 255
Timer
TIMEOUT
Timer-x, x = 00 to 23
Max value: 4,294,967,295 seconds
Schedule
Time, Range and Recurrence
Expansion
Module
Connection
Failure
0, 1
Virtual Channel =, >, <, >=, <=
VC-x represents the channel number
System Start up N/A
Activate when the system is starting up at
System Start