Description of functions
57
Description of functions
Phase reversal
Three-phase motors work with clockwise rotating fields (viewed
from the motor shaft) when phase L1 is connected to U1, L2 to V1
and L3 to W1. This default operating direction may be reversed
through gearboxes or different mounting positions. With the
reversing starter, the operating direction can be reversed with the
phase reversal switch (pole 7 of the DP switch under the front
locking screw,
table 5, page 63) without rewiring or
reprogramming.
With control signal FWD (LED FWD lit) a clockwise rotating field is
output in switch position Top (default) and an anticlockwise
rotating field in switch position Bottom.
Quick stop and interlocked manual mode
Motor starter RA-MO...4 has two external inputs, through which
two light barriers, sensors or limit switches can be connected. You
can configure these inputs as Quick Stop or Interlocked Manual
operation with DIP switches.
The Quick Stop function allows precision stopping of the drive.
When the limit switch is reached, the drive switched off directly
through preprocessing of the motor starter. PLC and bus cycle
times do not affect the power-off times. From version 2.x the
power-off times are even shorter and more precise than in version
1.x.
From version 2.x and depending on your application, there are
several ways of configuring the Quick Stop function:
• From Version 2.1:
– Input I3 acts on both directions of rotation and I4 has no
additional function.
– Input I3 acts on Forward direction and I4 on Reverse
direction.
• New from version 2.2:
– Inputs I3 and I4 act in Forward direction.
Interlocked manual mode can prevent damage to the conveyed
material and the plant in also manual operation. If you have
selected this function, limit switch I3 limits the possible forward
travel and limit switch I4 limits the possible reverse travel.
If the material reaches the limit switch in Manual mode, the drive
stops even if the selector switch remains in an actuating position.
In addition you can use this function to adjust the light barriers
before commissioning the PLC.
Figure 60: Direction of rotation
L1L2L
3
1 7
3
U V W
FWD
FWD
L1 L2 L
3
1 7
3
U V W
FWD
ON
7
ON
7
h
The version number is printed under “Ver-No.:” on the
nameplate,