01/08 AWB2190-1430GB
RA-SP and keypad DEX-KEY-10
117
Jog Mode
0
A39
Jog Mode
= stop mode in jogging (inching) duty
Not used with RA-SP
rw
STOP
ADJ
80
b81
ADJ
= (Analog adjustment)
Not used with RA-SP
rw
online
PANEL
d01
b89
PANEL
= panel display value for DE5-KEY-R03.
d01
= actual frequency [Hz]
d02
= Motor current (I0) [A]
d03
= direction of rotating field (R, F)
d04
= PID actual value
d05
= Status of digital inputs (1 to 5)
d06
= status of digital outputs (fault signal, 11, 12)
d07
= display value [Hz] (output frequency
x
factor)
ro
rw
1)
–
online
1)
TERM LLL
LLLLL
–
TERM = (terminal) signal state of internal control inputs
H = (High) input/output energized
L = (Low) input/output not energized
LLL = Fault signal and internal message
HLLLL = PTC (function enabled)
HLLLH = PTC, switch positions HAND and FWD
HLLHL = PTC, switch positions HAND and REV
HLHLL = PTC, switch positions AUTO and AS-Interface
®
Q2 = 1
HHLLL = PTC, switch positions AUTO and AS-Interface
®
Q3 = 1
HHHLL = PTC, switch positions AUTO and AS-Interface
®
Q2 = 1 and Q3 = 1
ro
–
ERR1
---
–
ERR1 = last fault message
_ _ _ = Type of detected fault, frequency on fault, current on fault, DC link
voltage on fault [Vdc]
ro
–
ERR1
0.0Hz
–
0.0Hz = frequency on fault ERR1
ro
–
ERR1
0.0A
–
0.0A = current on fault ERR1
ro
–
ERR1
000.0Vdc
–
000.0Vdc = DC link voltage on fault ERR1
ro
–
ERR1 RUN 000000H
–
RUN 000000H = operating hours on fault ERR1
ro
–
ERROR COUNT
000
–
ERROR COUNT 000 = number of faults to date
ro
–
ERR2
---
–
ERR2 = last but one fault message; additional indication as for ERR1
ro
–
ERR3
---
–
ERR3 = second from last fault message, additional indication as for ERR1
ro
–
You can configure the Monitor menu to display the following additional information:
FS 000.0F
0.0Hz
–
FS
= frequency setpoint through keypad DEX-KEY-10
rw
online
1S 000.0F
0.0Hz
1S
to
3S
= fixed reference frequency 1 to 3 (4 to 15 are not used with RA-SP)
ro
–
ACC2
0015.0S
A92
ACC1 = second acceleration time from 0 Hz to end frequency; displayed only
when enabled (
a
F06)
rw
online
DEC2
0001.5S
A93
DEC2
= second deceleration time from end frequency to 0 Hz; displayed on ly
when enabled (
a
F06)
rw
online
PNU = parameter number of frequency inverter DF5
ro = parameter is read-only
rw = parameter is read/write
online = changed values take effect immediately
STOP = settings can be changed only at standstill (output frequency = 0: selector switch in OFF position or STOP key pressed).
Display text
DF5
PNU
Meaning
Access