01/08 AWB2190-1430GB
RA-SP and keypad DEX-KEY-10
121
DCB SW
OFF
A51
DC braking
•
OFF
= 00 (inactive)
•
ON
= 01 (active)
OFF, ON
OFF
DCB F
00.5Hz
A52
Startup frequency
0.5 to 10 Hz
0,5
DCB WAIT
0.0s
A53
Waiting time
0 to 5 s
0
DCB V
000
A54
Braking torque
0 to 100 %
0
DCB T
00.0s
A55
Braking duration
0 to 60 s
0
F-22
IPS
Mains failure duration
IPS UVTIME 01.0s
b02
Permissible mains failure duration
0,3 to 25 s
5
IPS WAIT 001.0s
b03
Waiting time before restart
0,3 to 100 s
1
IPS POWR
ALM
b01
Restarting mode
•
ALM
= 00 (no automatic starting after a fault
message)
•
ZST
= 01 (with 0 Hz)
•
RST
= 02 (synchronization and acceleration)
•
FTP
= 03 (synchronized and deceleration to 0 Hz)
ALM, ZST, RST,
FTP
ALM
F-23
E-THM
Electronic motor protection device
E-THM CHAR
CRT
b13
Motor protection - characteristic
•
CRT
= 01 (constant)
•
SUB
= 00 (enhanced)
CRT, SUB
CRT
E-THM LVL 00.00A
b12
Tripping current (
I
e
= rated operational current of
frequency inverter)
0,5 to 1,2
x
I
e
[A]
on
F-24
OLOAD
Current limit
OLOAD LVL 00.00A
b22
Tripping current
0,5 to 1,5
x
I
e
[A]
on
OLOAD CONST 01.0
b23
Time constant
0,1 to 30 Hz/s
1
OLOAD MODE
b21
Motor current limitation
•
OFF
= 00 (inactive)
•
ON
= 01 (active)
•
CRT
= 02 (inactive during acceleration)
OFF, ON, CRT
ON
F-25
S-LOCK
b31
Parameter protection
•
MD0
= 00 (with SFT digital input; all functions
inhibited)
•
MD1
= 01 (with SFT digital input; all functions except
PNU F01 inhibited)
• MD2 = 02 (without SFT digital input; all functions
inhibited)
• MD3 = 03 (without SFT digital input; all functions
except PNU F01 inhibited)
MD0, MD1,
MD2, MD3
MD1
F-26
LIMIT
Frequency limit values
LIMIT H 000.0Hz
A61
Maximum operating frequency
0 to 360 Hz
0
LIMIT L 000.0Hz
A62
Minimum operating frequency
0 to 360 Hz
0
F-27
JUMP
Frequency jump
JUMP F1 000.0Hz
A63
1st frequency jump
0 to 360 Hz
0
JUMP F2 000.0Hz
A65
2st frequency jump
0 to 360 Hz
0
JUMP F3 000.0Hz
A67
3st frequency jump
0 to 360 Hz
0
JUMP W1
00.5Hz
A64
Jump width of the 1st frequency jump
0 to 10 Hz
0
JUMP W2 00.5Hz
A66
Jump width of the 2st frequency jump
0 to 10 Hz
0
DEX-KEY-10
Fn No./indication
DF5
PNU
Meaning
(display code DF5)
Value range
FS
a
Page
Summary of Contents for Rapid Link
Page 10: ...01 08 AWB2190 1430GB 6 ...
Page 40: ...01 08 AWB2190 1430GB 36 ...
Page 48: ...01 08 AWB2190 1430GB 44 ...
Page 70: ...01 08 AWB2190 1430GB 66 ...
Page 146: ...01 08 AWB2190 1430GB 142 ...
Page 162: ...01 08 AWB2190 1430GB 158 ...