01/08 AWB2190-1430GB
Installation of flexible busbar
RA-C1-7x…
21
Establishing connections
The feeder and busbar junction modules can be fitted at any point
along the flexible busbar. The conductors of the flexible busbar
remain uninterrupted. The connection is established with contact
screws.
Fitting feeder and junctions
Because of its symmetry, flat cable feeders and junctions can be
fitted on either side of the flexible busbar.
Fit the flexible busbar, ensuring correct polarity, close the upper
section and secure it with screws.
The installation is demonstrated here with flexible busbar power
supply and junction RA-C1-VP-SR; flexible busbar junction RA-C1-
PLF and flexible busbar power supply and junction RA-C1-AM-7
for the flexible busbar are fitted in the same way.
X
Secure the module to the subsurface with suitable screws, e.g.
M4 using the provided slots.
X
Flip open the top and insert the flexible busbar.
X
Close the top and screw it shut.
The top section is now protected to IP65.
Pin
Function
wire colours
7
x
2,5 mm
2
wire numbers
7
x
4 mm
2
1
L1
black
1
2
L2
brown
2
3
L3
black
3
4
N
blue
4
5
+24 V
red
5
6
0 V
white
6
PE
PE
green/yellow
green/yellow
Figure 19: Terminal assignment of flat cable busbar junction
RA-C1-VP-PLF or
RA-C1-PLF
Figure 20: Connection assignment of the RA-C24-VP-AM-2 V
connection module
Figure 21: Terminal assignment of flat cable busbar power supply and
junction RA-C1-VP-SR
L2 L3
N L1 PE
M
L+
L+
M
L+
M
N
L1
PE
L2
L3
j
Warning!
Connection and disassembly work must be performed
only when the busbar is not live!