System Rapid Link
01/08 AWB2190-1430GB
24
X
Now fit the second radially split seal around the cable sheath at
the other cable end and insert it into the u-contour.
X
Place the cover onto the lower section so that it sits across its
entire surface without pivoting. If this is not possible, one or
more screws have not been fully tightened.
X
Secure the cover with the four screws
(size Pozidriv 2; tightening torque 1.5 to 2 Nm).
X
To ensure IP65, fit a cable tie about each seal and pull it tight.
X
Finally fit the supplied locking clip to the two studs on the
bushing enclosure.
X
Make sure that the round cable is laid in such a way that no
tensile force acts on it.
You can now connect the assembled plug of Rapid Link function
module RA-…/C2 and secure it with the clip. If you are using
ruand cable junction RA-C2-S2-4, fit function modules RA-…/C2
into both distributor sockets.
Pin
Func.
1
L1
2
L2
3
L3
e
e
4
N
5
24 V
6
0 V
Pin
Function
1
N
2
L2
3
N/A
4
+24 V (brake)
5
0 V (brake)
6
L3
7
–
8
L1
PE
PE
1
2
3
4
5
6
h
Close the open seal of the last round cable junction at the
end of the power bus with end-piece RA-C2-SBL.
Figure 22: RA-C2-S1-4
Figure 23: RA-C2-S2-4
i
Attention!
Before switching on the 400 V ~ and 24 V
H
power
supplies, check that all strands are securely connected to
the correct terminal. The PE conductor must be connected
to the middle terminal.
To identify possible wiring faults in the 24 V DC circuit,
switch on the 24 V DC voltage and, using the LED display
on the motor starters, check whether control voltage is
applied. If all UV LEDs are lit, you can connect the 400 V AC
supply.
L1 L2 L3
N 24 V 0 V
L1 L2 L3
N 24 V 0 V
Summary of Contents for Rapid Link
Page 10: ...01 08 AWB2190 1430GB 6 ...
Page 40: ...01 08 AWB2190 1430GB 36 ...
Page 48: ...01 08 AWB2190 1430GB 44 ...
Page 70: ...01 08 AWB2190 1430GB 66 ...
Page 146: ...01 08 AWB2190 1430GB 142 ...
Page 162: ...01 08 AWB2190 1430GB 158 ...