© MOBATIME
85 / 96
800337.22
E.5
SINEC – Telegram
Byte: Meaning: Character:
HEX Code:
1 Start
character
<STX>
02
2 Date
identifier
D
44
3 Separator
1
:
3A
4 Day
tens
0..3
30..33
5 Day
units
0..9
30..39
6 Separator
2
.
2E
7
Month tens
0 / 1
30 / 31
8 Month
units
0..9
30..39
9 Separator
2
.
2E
10 Year
tens
0..9
30..39
11 Year
units
0..9
30..39
12 Separator
3
;
3B
13 Weekday
identifier
T
54
14 Separator
1
:
3A
15 Weekday
(Mo..Su)
1..7
31..37
16 Separator
3
;
3B
17 Time
identifier
U
55
18 Separator
1
:
3A
19 Hours
tens
0..2
30..32
20 Hours
units
0..9
30..39
21 Separator
2
.
2E
22 Minutes
tens
0..5
30..35
23 Minutes
units
0..9
30..39
24 Separator
2
.
2E
25 Seconds
tens
0..5
30..35
26 Seconds
units
0..9
30..39
27 Separator
3
;
3B
28 Status
1
#:
No synchronization since last reset
<SP> / #
20 / 23
29 Status
2
*:
Free running based on internal quartz
<SP> / *
20 / 2A
30 Status
3
S:
Summer (daylight saving time, season time)
U: UTC
time
<SP> / S / U
1)
20 / 53 / 55
1)
31 Status
4
!:
Season change announcement during 1 h
<SP> / !
20 / 21
32
Telegram end character
<ETX>
03
1)
If the output of the character 'U' for UTC time should be suppressed, a user specific time zone table
with the corresponding entry 00 should be loaded to the ETC (Appendix C and Chapter 17.5).
Instead of the entry 00, the user defined entry (position 80 or higher) shall be selected in the menu of
the serial interface.