12.4 Impulse
Line
12.4.1 Change of the Line State
Sets the line state of the pulse line:
MENU
Clock
Lines
Line
X
[Impulse]
State:
Selection from:
stop, run, 12:00
In state
Stop
there’s no pulse output (pulse line stopped). The state
Run
shifts the pulse
line in normal operation (pulse output as set in the configuration).
In state
12:00
there’s send out as many pulses as the clock is reaching the adjusted
backlash periodicity. This state serves the clock to reach a defined position for
maintenance:
backlash periodicity:
behaviour:
60 sec
Pulse output in backlash speed, until xx:xx:00 is
reached.
(function insignificant).
12 h
Pulse output in backlash speed, until 12:00 is reached.
24 h
Pulse output in backlash speed, until 00:00 is reached.
1 week
(function insignificant)
12.4.2 Line
Time
In order to be able to set the slave clocks of an impulse line onto the master clock time,
the line must first be stopped (state: stop), then all the hands of the slave clocks must be
set to the same position. Set the line time manually to the time displayed on slave clocks
(see menu below) and start the line again.
MENU
Clock
Lines
Line
X
[Impulse]
Time:
If some slave clocks lack one step (1 second, ½-minute,
1
/
5
-minute,
1
/
8
-minute or 1
minute) the polarity of the line has to be changed at these particular clock connections.
Afterwards the clocks shall be set again as per the above mentioned procedure.