12.6.3 Line
Time
To set the slave clocks of an impulse line to the master clock time, the line must first be
stopped (state: stop). Then all the hands of the slave clocks must be set to the same
position. Set the line time manually to the time displayed on slave clocks (see menu
below) and start the line again.
MENU
Clock
Lines
Line
X
[DCF-Imp]
Time:
If some slave clocks lack one step (1 minute), the polarity of the line has to be changed
at these particular slave clock connections. Afterwards the clocks shall be set again as
per the above mentioned procedure.
12.6.4 Line
Date
The line date is only important for calendar clocks with a catch-up periodicity of one week
and is therefore not essential to set.
MENU
Clock
Lines
Line
X
[DCF-Imp]
Date:
12.6.5 Time
Zone
Setting of the time zone for this output line.
...
Line
X
[DCF-Imp]
Configuration
Time
zone:
The cursor keys
/
are used for selection from the 100 possible entries, or the
time zone can be selected by means of a numerical input (refer to annexe C).
12.6.6 Line
Mode
Selection of
min
or
1/2 min
for the output of polarized minute or ½ -minute impulses.
...
Line
X
[DCF-Imp]
Configuration
Line
mode:
The resulted impulse interval is therefore in normal operation 60, 30 seconds
respectively.