160
(4) External power supply
• Use a CE-marked product for an external power supply and always ground the FG terminal. (External power
supply used for the tests conducted by Mitsubishi: TDK-Lambda DLP-120-24-1, IDEC PS5R-SF24, PS5R-
F24)
• Use a power cable of 10m or shorter when connecting it to the module power supply terminal.
(5) Others
(a) Ferrite core
A ferrite core has the effect of reducing radiated noise in the 30MHz to 100MHz band.
It is recommended to attach ferrite cores if shielded cables coming out of the control panel do not provide
sufficient shielding effects.
Note that the ferrite cores must be attached at the position closest to the cable hole inside the control panel. If
attached at an improper position, the ferrite core will not produce any effect.
For the FG terminal on a main module that is connected to the external power supply, the external power
supply of an extension module, and CC-Link IE Field Network cables, attach a ferrite core 4cm away from the
module.
(Ferrite core used for the tests conducted by Mitsubishi: NEC TOKIN ESD-SR-250, TDK ZCAT3035-1330)
Example
Summary of Contents for NZ2GF2B-60DA4
Page 1: ......
Page 2: ......
Page 44: ...42 Memo...
Page 117: ...115 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo...
Page 167: ...165 APPENDICES A Appendix 9 External Dimensions Memo...
Page 173: ......
Page 174: ......