Set a value for CH
Shifting set value (RWw6 to RWw9).
The default value of the shifting set value is "0".
If the digital value exceeds the range of -32768 to 32767 as a result of shift addition, the digital operation value is fixed to the
lower limit value (-32768) or the upper limit value (32767).
(3) Setting example
Ex.
When the following settings are used for a channel with output range of -10 to 10V:
• CH
Shifting set value (RWw6 to RWw9): 250
The digital value is as follows:
Item
Setting range
CH
Shifting set value (RWw6 to RWw9)
-32768 to 32767
Analog output voltage (V)
Digital value
(before adjustment)
Digital value + Shifting set value
(after adjustment)
-10
-16250
-16000
-5
-8250
-8000
0
-250
0
5
7750
8000
10
15750
16000
10
5
0
0
16000
15750
-16000
-16250
-5
Analog output voltage (V)
Adjust with the shifting set value.
Digital value
-10
Add the shifting set value.
1) Digital value
(before adjustment)
2) Digital value + Shifting set
value (after adjustment)
1) Digital value
(before
adjustment)
2) Digital value +
Shifting set value
(after adjustment)