100
(4) Setting procedure
Ex.
When setting the assignment explained in the previous page
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
Select a D/A converter module in "List of stations"
[CC IE
Field Configuration]
[Parameter Processing of Slave Station]
2.
Set "CH
D/A conversion enable/disable setting" to "0: Enable".
3.
Set "CH1 Alert output setting" to "0: Enable".
4.
Set values for "CH1 Alert output upper limit value" and "CH1 Alert output lower limit value".
5.
Set 0x002A ("2A" of RY2A) for "Alert output signal assignment".
●
Signals other than remote I/O signals assigned to the external module cannot be set with the external signal assignment
function.
If the above is set, the error code (017
H
) is stored in Latest error code (RWr0), Error flag (RXA) turns on, and the ERR.
LED turns on.
●
Multiple remote I/O signals of the main module cannot be assigned to a remote output signal of the extension module.
If the above is set, the error code (0180
H
) is stored in Latest error code (RWr0), Error flag (RXA) turns on, and the ERR.
LED turns on.
●
The external signal assignment function cannot be used together with the digital output HOLD/CLEAR function.
When "Digital output HOLD/CLEAR setting" is set to "1: HOLD", the setting is ignored and the D/A converter module
operates with "0: CLEAR" set.