80
(3) Setting procedure
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
Select a D/A converter module in "List of stations"
[CC IE Field Configuration]
[Parameter Processing of Slave Station]
2.
Set "CH
D/A conversion enable/disable setting" to "0: Enable".
3.
Set "CH
Scaling enable/disable setting" to "0: Enable".
4.
Set values for "CH
Scaling lower limit value" and "CH
Scaling upper limit value".
●
Even if the scaling upper limit value and the scaling lower limit value are set so that the change is larger than the
maximum resolution described in the performance specifications, the resolution will not increase.
●
Scaling settings must meet the following condition:
Scaling upper limit value > Scaling lower limit value
Item
Setting range
CH
Scaling upper limit value
-32000 to 32000
CH
Scaling lower limit value
Summary of Contents for NZ2GF2B-60DA4
Page 1: ......
Page 2: ......
Page 44: ...42 Memo...
Page 117: ...115 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo...
Page 167: ...165 APPENDICES A Appendix 9 External Dimensions Memo...
Page 173: ......
Page 174: ......