130
(3) When the ON/OFF status of the remote output (RY) set in the external signal
assignment function does not match the signal of the assigned function.
Check item
Action
Is the setting of the external signal assignment
function correct?
Check that the following settings are not used in the external signal assignment
function.
• Alert output signal assignment (address: 0004
H
) (
• Error flag assignment (address: 0005
H
) (
• Warning flag assignment (address: 0006
H
) (