145
APPENDICES
A
Appendix 3 Details of R
emote Buffer
Memory Areas
(8) Range setting (address: 0103
H
)
The output range is set for each channel.
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9).
(b) Default value
The default value is set to 4 to 20mA (0
H
).
If data other than the above is set, an error occurs. The error code (010
H
) is stored in Latest error code (RWr0), Error flag
(RXA) turns on, and the ERR. LED turns on.
(9) Analog output HOLD/CLEAR setting (address: 0104
H
)
Whether to hold or clear the analog value that is output at the state of CPU module being RUN, STOP, or when
an error occurs, is set for each channel.
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9).
(b) Default value
The default value is CLEAR (0
H
).
Output range
Setting value
4 to 20mA
0
H
0 to 20mA
1
H
1 to 5V
2
H
0 to 5V
3
H
-10 to 10V
4
H
User range setting 1 (-10 to 10V)
5
H
User range setting 2 (0 to 20mA)
6
H
Analog output HOLD/CLEAR setting
Setting value
CLEAR
0
H
HOLD
1
H
to F
H
(a number other than 0)
b15
to
b12 b11
to
b8 b7
to
b0
to
b3
b4
CH1
CH2
CH3
CH4
b15
to
b12 b11
to
b8 b7
to
b0
to
b3
b4
CH1
CH2
CH3
CH4
Summary of Contents for NZ2GF2B-60DA4
Page 1: ......
Page 2: ......
Page 44: ...42 Memo...
Page 117: ...115 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo...
Page 167: ...165 APPENDICES A Appendix 9 External Dimensions Memo...
Page 173: ......