101
CHAPTER 8 FUNCTION
8
8.11 F
unction
at the Extension Modu
le Installation
(a) Operation of when an error occurs
The operation of the D/A converter module for an error depends on whether or not the external signal
assignment function is used, as show in the following table.
*1
When the external signal assignment function is used, the operation of the D/A converter module is the same as that of
when the CLEAR is set for the digital output HOLD/CLEAR setting function, even if HOLD is set.
When different types of errors occur, an error is received in the following priority order.
• Major error > Moderate error > Minor error > the error at the time of Disconnecting or CPU STOP
Remote I/O signal
Remote input (RX)
Remote output (RY)
Digital output HOLD/CLEAR
setting function
-
CLEAR
HOLD
External signal assignment
function
Used
Unused
Used
Unused
Used
Unused
*1
Status of the
D/A converter
module
Minor error
Same as the normal operation
Same as the normal operation
Same as the normal operation
Moderate error
Clear
Clear
Clear
Same as the
normal
operation
Clear
Same as the
normal
operation
Major error
Clear
Clear
Clear
Disconnecting
or CPU STOP
Clear
Clear
Clear
Same as the
normal
operation
Hold
Same as the
normal
operation
Summary of Contents for NZ2GF2B-60DA4
Page 1: ......
Page 2: ......
Page 44: ...42 Memo...
Page 117: ...115 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo...
Page 167: ...165 APPENDICES A Appendix 9 External Dimensions Memo...
Page 173: ......
Page 174: ......