96
*1
A warning is in the following state five seconds after the error cause is removed.
• Warning flag (RX7) turns off.
• Latest warning code (RWr1) is cleared.
• The ERR. LED turns off.
*2
The alarm is not automatically cleared. Latest warning code (RWr1) is cleared when the other minor errors are cleared in
the alarm status.
The warning codes can be checked in the error history on GX Works2. For the error history, refer to the following.
• Checking by executing a command of the slave station (
• Error history
(address: 0A00
H
to 0AEF
H
) (
Ex.
Operation to clear Station number switch changing error (error code: 0940
H
)
For the method for clearing an alarm, refer to the following.
• Digital Value Range Check Function (
• Alert Output Function (
Station No.1
(normal)
Station No.1 (normal)
ON
ON
OFF
OFF
Warning flag (RX7)
Station number setting
switch
Latest warning code
(RWr1)
ERR. LED
Remote READY
(RXB)
OFF
Station No.10 (error)
OFF
0
Flashing
0
5 seconds
0940
H
(station number switch changing error)
Controlled by the D/A converter module