Error
Cause
Possible remedy
WS0-GETH functioned
correctly after configuration, but
suddenly no longer supplies
data.
LED PWR
Green
LED LINK/ACT
/
Green
LED MS
Red/Green
WS0-GETH is operated in slave
mode, the IP address is assigned
from a DHCP server. After the WS0-
GETH or the DHCP server has been
restarted, a different IP address that
is unknown to the programmable
controller has been assigned to the
WS0-GETH.
Either assign a fixed IP address to the WS0-
GETH, or reserve a fixed IP address for the
WS0-GETH in the DHCP server (manual
assignment by means of the MAC address of
the WS0-GETH).
WS0-GETH/safety controller is
in Critical fault mode.
LED PWR
Green
LED LINK/ACT
Green
LED MS
Red
WS0-GETH is not plugged properly
into the other MELSEC-WS module.
Module connection plug is soiled or
damaged.
Other MELSEC-WS module has
internal critical error.
Ethernet communication with the
WS0-GETH is under excessive load.
Plug the WS0-GETH in correctly.
Clean the connecting socket/plug.
Repower the safety controller.
Check the error MELSEC-WS module and
remove the error cause.
Check the Ethernet line status. If a load is
excessively placed to the line, reduce the load
using a device such as a router.
WS0-GETH is in Critical fault
mode.
LED PWR
Green
LED LINK/ACT
/
Green
LED MS
Red (2 Hz)
WS0-GETH internal device error
Switch off the power supply of the safety
controller and switch it on again.
Check if the WS0-GETH is mounted in correct
position.
Check the diagnostics messages with the
Setting and Monitoring Tool.
If the error remains, replace the Ethernet
interface module.
Summary of Contents for Melsec WS Series
Page 1: ...Safety Controller Ethernet Interface Module User s Manual WS0 GETH ...
Page 2: ......
Page 89: ...Procedures before operation MELSEC WS 86 ...
Page 90: ...MELSEC WS Procedures before operation 87 ...
Page 91: ...Procedures before operation MELSEC WS 88 ...
Page 97: ...Procedures before operation MELSEC WS 94 ...
Page 98: ...MELSEC WS Procedures before operation 95 ...
Page 99: ...Procedures before operation MELSEC WS 96 ...
Page 141: ......