Procedures before operation
MELSEC-WS
114
(3) Monitoring data with Setting and Monitoring Tool
The written output data sets can be monitored in the
Ethernet to CPU
dialog of
Setting and Monitoring Tool. For the execution result of the program, refer to
Section 8.2.3 (3).
8.3.4
Auto update mode
This section describes an example of communications in auto update mode.
The Built-in Ethernet port QCPU reads MELSEC-WS safety controller information
(e.g. logic result, CRC, and each module status) from the safety controller through
communications between the WS0-GETH and the QJ71E71-100. The WS0-GETH
automatically sends input data sets to the QJ71E71-100 at 5000-ms intervals.
Read-target data
Logic result 0 (input data set 1)
CRC (input data set 2)
Each module status (input data set 3)
Figure 66: System configuration example
(1) Parameter configuration
(a) Configuration required for the WS0-GETH
Configuration examples of network parameters required for communications in
auto update mode are shown below. Configure these parameters using Setting
and Monitoring Tool.
The WS0-GETH requires no program for communications.
1) Creating a hardware configuration
Refer to Section 8.2.2 (1).
2) Assigning an IP address
Refer to Section 8.2.2 (1).
Summary of Contents for Melsec WS Series
Page 1: ...Safety Controller Ethernet Interface Module User s Manual WS0 GETH ...
Page 2: ......
Page 89: ...Procedures before operation MELSEC WS 86 ...
Page 90: ...MELSEC WS Procedures before operation 87 ...
Page 91: ...Procedures before operation MELSEC WS 88 ...
Page 97: ...Procedures before operation MELSEC WS 94 ...
Page 98: ...MELSEC WS Procedures before operation 95 ...
Page 99: ...Procedures before operation MELSEC WS 96 ...
Page 141: ......