Parameter
Length
Value
Command WORD
00E1
H
= Auto update control
Request data set 1
WORD
0 = Do not send data set 1.
1 = Send data set 1.
Request data set 2
WORD
0 = Do not send data set 2.
1 = Send data set 2.
Request data set 3
WORD
0 = Do not send data set 3.
1 = Send data set 3.
Request data set 4
WORD
0 = Do not send data set 4.
1 = Send data set 4.
Auto update mode
update rate
WORD
0 = Disable auto update messages.
Non-zero = Enable auto update message at
specified rate in ms. (If the value is 40 or
less, data sets are sent at 40ms
interval.)
Minimum = 40 ms, Maximum = 65535 ms
Auto update is disabled if all Request Input Data Set flags are set to zero.
The response message returned to the application by the Ethernet interface module:
Parameter Length
Value
Command WORD
001E
H
= Response to the auto update control message
Configuration via Setting and Monitoring Tool
In order to configure the auto update mode of the Ethernet interface module via the
Setting and Monitoring Tool, perform the following steps:
Open the Setting and Monitoring Tool and load the hardware configuration
including the Ethernet interface module.
Click on the
GETH Network module [13]
button
(
Network Modules
button
when two network modules are used) above the main window and select the
desired network module or double click on the desired network module in the
hardware configuration view to open the network module configuration dialog.
Click on
TCP/IP configuration
on the left hand menu. The following dialog
appears:
Table 10:
Auto update mode
configuration command
Note
Table 11:
Auto update mode
configuration response
Summary of Contents for Melsec WS Series
Page 1: ...Safety Controller Ethernet Interface Module User s Manual WS0 GETH ...
Page 2: ......
Page 89: ...Procedures before operation MELSEC WS 86 ...
Page 90: ...MELSEC WS Procedures before operation 87 ...
Page 91: ...Procedures before operation MELSEC WS 88 ...
Page 97: ...Procedures before operation MELSEC WS 94 ...
Page 98: ...MELSEC WS Procedures before operation 95 ...
Page 99: ...Procedures before operation MELSEC WS 96 ...
Page 141: ......