20
- 20
20.3 ERROR MESSAGE AND SYSTEM ALARM
20.3.2 List of Error Message/System Alarm
317
Too high frequency of
data collection.
Review conditions.
Data of an object, to which [Collect data only when trigger
conditions are satisfied] is set, are collected too frequently, or
the number of objects has exceeded the number of objects
collectable simultaneously.
1. Set a longer cycle for trigger occurrence to each object.
2. Make the settings so that 257 or more display triggers of
objects, to which [Collect data only when trigger
conditions are satisfied] is set, do not occur
simultaneously.
320
Specified object does not
exist or out of range.
The part file does not exist.
Create the part file and download to GOT.
322
Dedicated device is out of
range. Confirm device
range.
The monitored device No. is out of the permissible area of the
targeted PLC CPU.
Set the device within the range that can be monitored by the
monitored PLC CPU and parameter settings.
330
Insufficient memory media
capacity. Confirm M-card
capacity.
Available memory of the memory card is insufficient.Confirm
the available memory of the memory card.
The available memory can be confirmed by system
information screen, which is described in GT Designer2
Version Screen Design Manual.
331
Memory card not installed
or M-CARD switched OFF
The memory card is not installed or in the drive access switch
is OFF in drive.
1. Install the memory card in the specified drive.
2. Turn ON the access switch.
332
Memory media is not
formatted.
Memory card is not formatted or formatted incorrectly.
Format the memory card.
333
Unable to overwrite.
Memory card is write-
protected.
Memory card is write-protected.
Cancel the write-protection of memory card.
334
Memory media error.
Replace memory media.
Memory card is faulty.
Replace the memory card.
335
Memory card battery
voltage low. Replace
battery.
The battery voltage of the memory card is low.
Replace the battery of the memory card.
337
File output failed. Confirm
output file path.
Either of the following folder or file with the name same as the
file to be created exists in the storage destination memory
card.
Folder storing data
Write-protect file
Delete the above folder or file, or change the name of the file
to be created.
340
Printer error or power
failure
Printer is faulty or the printer power supply has not been
turned on.
1. Confirm the printer.
2. Turn on the power supply of the printer.
Error
code
Error message
Action
Channel
No.
storage