8
- 18
8.2 RS-422 Conversion Unit
8.2.1 Applicable RS-422 conversion unit
8.2 RS-422 Conversion Unit
The RS-422 conversion unit is inserted to the GOT RS-232 connector to enable the RS-422 communication
by RS-232/RS-422 conversion.
Refer to the following for the details of connection statuses.
GOT1000 Series Connection Manual
8.2.1
Applicable RS-422 conversion unit
The following RS-422 conversion units are applicable for GT15
.
Notes on using the RS-422 conversion unit
1. Use GT15-RS2T4-25P when you switched to use from the GOT-A900 series.
Use GT15-RS2T4-9P when you newly use the GOT1000 series.
2. Set to [ON] by [5V supply] at [Communication settings] of the utility.
(
10.1.4 Communication setting display operation)
8.2.2
Installing procedure
1
Power OFF the GOT.
2
Installs the RS-422 conversion unit in the RS-232 interface of the GOT rear face.
3
Tighten the fixing screws in the specified torque range (0.36 to 0.48N·m) after the installation.
Model name
Description
GT15-RS2T4-9P
RS-232-RS-422
conversion unit
RS-422 side connector 9 pins
(15", 12.1", 10.4", 8.4")
GT15-RS2T4-25P
RS-422 side connector 25 pins
(15", 12.1", 10.4", 8.4")