![MIOX RIO-S Series Installation, Operation And Maintenance Manual Download Page 64](http://html1.mh-extra.com/html/miox/rio-s-series/rio-s-series_installation-operation-and-maintenance-manual_1804803064.webp)
MIOX RIO-S Series Operators Manual
102-00130-D
Page
64
Quarterly Maintenance
Clean Brine Tank
– Using a wet rag, wipe down the interior of the brine generator tank
wall to remove any dirt or buildup.
Clean or Replace the Brine Filter and Water Filter
– The brine and water filters are the
same 5-micron standard type unit for removal of particulate matter. The brine filter and
water filter are located prior to the water softener or OSG. The OSG should be off or in
STOP mode when filters are removed or replaced. Visually inspect the filter for clogging and
debris. If flow is restricted, the filter should be replaced. Reinstall the filter. Discard the old
filters according to local environmental codes.
Cell Bank Acid Wash
– Refer to 102-00012 for procedure for cleaning cells utilizing an acid
wash.
Check Controls Wiring Connections
– Electrical heating and cooling cycles may loosen
connections. After turning OSG power off, check all connections for tightness by gently
tugging on them. Tighten any loose screws or bolts. Wires should be clean, dry, and
corrosion-free.
Yearly Maintenance
Drain and clean the brine generator every year to remove build-up that can be up to several
inches thick. Drain and clean the oxidant solution tank annually to remove particulates.
Avoid any ignition sources in the vicinity of the oxidant solution tank.