MIOX RIO-S Series Operators Manual
102-00130-D
Page
11
The oxidant storage tank is an integral part of an on-site generator and is sized to meet the
injection demand at the peak hourly flow. The oxidant tank must be vented directly to the
atmosphere outside the facility.
Brine Pressure Boost System
A brine pressure boost system insures that sufficient brine pressure is supplied to the brine
metering pump to maintain optimal cell operation amperage. A separate electrical circuit is
required for the brine boost system.
Plumbing and Fittings
All plumbing and fittings shipped by MIOX meet Schedule 80 specifications. The U.S.
specifications ensure that materials are rated for proper thickness, pressure requirements,
and temperature resistance for the specific application.
RIO-S Series OSG System Optional Equipment
Heater or Chiller
If the OSG feed water temperature is less than 40°F (5°C) or greater than 95°F (35°C),
damage to the electrolytic cell will occur. A water heater or chiller is recommended to bring
the water temperature into range.
Oxidant Solution Injection System
MIOX can supply injection systems to dose raw water with disinfectant. These systems
come with separate installation and operation instructions.
Water Pressure Boost System
A water pressure boost system can be included to insure minimum water pressure for OSG
operation and support of water softener regeneration. A separate electrical circuit is
required for the water pressure