68
Pellerin Milnor Corporation
Table 14
Interpretation of Test DIP Switch Display (cont'd.)
Displayed Value
Switch Settings
Industry
1
2
3
4
5
6
7
8
230
1
0
0
1
1
0
0
0
Shirt Laundries
231
0
0
0
1
1
0
0
0
Offshore Laundries
232
1
1
1
0
1
0
0
0
Gear Guardian
240
1
1
1
1
0
0
0
0
Correctional
241
0
1
1
1
0
0
0
0
Hotel/Motel
242
1
0
1
1
0
0
0
0
Athletic
243
0
0
1
1
0
0
0
0
Healthcare Facilities
244
1
1
0
1
0
0
0
0
Restaurants
245
0
1
0
1
0
0
0
0
Commercial Laundries
246
1
0
0
1
0
0
0
0
Shirt Laundries
247
0
0
0
1
0
0
0
0
Offshore Laundries
248
1
1
1
0
0
0
0
0
Gear Guardian
4.1.6
Testing Temperature and Level Sensors
BNCJHT01.C05 0000191882 C.2 F.3 A.9 1/2/20 1:16 PM Released
The
Test Temperature & Level
selection on the
Manual menu
is used primarily by the Milnor
®
factory for testing and calibration of machines before delivery. For testing a temperature or level
sensor in the field, the input to the sensor (level or temperature) must be controlled, but the sensor
must remain connected to the processor board. The temperature sensor can be tested with a con-
tainer of ice and water. A probe inserted in a container filled with ice and water will register ap-
proximately 32 degrees Fahrenheit (0 degrees Celsius).
Testing the pressure transducer requires a fixture similar to the one illustrated in
Sensor Testing Fixture, page 69
. As the graduated plastic tube from the transducer is lowered be-
low the surface of the water, the displayed level values rise. If the values don't change, verify that
there is absolutely no leaking in the pressure tube or at its connection to the transducer.