KE300A Inverter Parameter Description
80
P0-06
Auxiliary Frequency source B
range
Factory default
100%
Setting range
0% ~ 150%
When the frequency source selection is frequency combination reference (P0-07 is set to 1 or 3), the two
parameters are used to determine the adjustment range of auxiliary frequency source.
P0-05 is used to determine the relative object of that range. If it is relative to maximum frequency A, that
range will change with the main frequency A.
P0-07
Frequency source selection
Factory default
00
Setting range
Units
place
Frequency source selection
0
Main frequency source A
1
Calculation result of frequency A and B (determined by
tens place)
2
Switching between A and B
3
Switching between A and calculation result
4
Switching between B and calculation result
Tens
place
Calculation relationship between frequency A and B
0
A + B
1
A - B
2
Max (A, B)
3
Min (A, B)
Units place: Frequency source selection
0: Main frequency source A
Reference frequency = A
1: Calculation result of frequency A and B
Reference frequency = Calculation result of frequency A and B (determined by tens place)
2: Switching between A and B
If the multifunctional input terminal HDI (P4-0X=18:frequency switching) is invalid, reference frequency =
A.
If the multifunctional input terminal HDI (frequency source switching) is valid, reference frequency = B.
3: Switching between A and calculation result
If the multifunctional input terminal HDI (frequency switching) is invalid, reference frequency = A.
If the multifunctional input terminal HDI (frequency switching) is valid, reference frequency = calculation
result.
4: Switching between B and calculation result
If the multifunctional input terminal HDI (frequency switching) is invalid, reference frequency = B.
If the multifunctional input terminal HDI (frequency switching) is valid, reference frequency = calculation
result.