KE300A Inverter Function Parameter List
64
Function
code
Name
Detailed instruction
Factory
default
Modify
range)
P8-50
Wake up delay time
0.0s ~ 3600.0s
0.0s
○
P8-51
Dormancy frequency
0.00Hz ~ P0-10 (maximum frequency)
0.00Hz
○
P8-52
Dormancy delay time
0.0s ~ 3600.0s
0.0s
○
P8-53
Running arrival
time setting
0.0Min ~ 3600.0Min
0.0Min
○
P9 Group: Fault and Protection
P9-00
Motor overload protection
selection
0: Disable
1: Enable
1
○
P9-01
Motor overload protection
gain
0.20 ~ 10.00
1.00
○
P9-02
Motor overload pre-alarm
coefficient
50% ~ 100%
80%
○
P9-03
Stall over-voltage gain
0 ~ 100
0
○
P9-04
Stall over-voltage point /
Braking threshold
120% ~ 150%
130%
○
P9-05
Stall over current gain
1 ~ 100
20
○
P9-06
Stall over-current point
100% ~ 200%
160%
○
P9-07
Short-circuit to ground
protection selection when
power-on
0: Invalid
1: Valid
1
○
P9-08
Reserved
○
P9-09
Fault auto reset times
0 ~ 5
0
○
P9-10
Fault HDO acts selection
in fault auto reset
0: No action
1: Action
0
○
P9-11
Fault auto reset interval
0.1s ~ 100.0s
1.0s
○
P9-12
Input phase failure
protection selection
0: Disable
1: Enable
1
○
P9-13
Output phase failure
protection selection
0: Disable
1: Enable
1
○
P9-14
The first fault type
0: No fault
1: Reserved
2: Acc over current
3: Dec over current
4:
Over current in constant speed
5:
Over voltage in Acc process
6:
Over voltage in Dec process
7:
Over voltage in constant speed
-
●