KE300A Inverter Parameter Description
120
Jump frequency amplitude
Jump frequency
2
Jump frequency
1
Output frequency (
Hz)
Time (t)
Jump frequency amplitude
Jump frequency amplitude
Jump frequency amplitude
Figure 6-13 Jump frequency diagram
P8-12
FWD/REV dead time
Factory default
0.0s
Setting range
0.00s ~ 3600.0s
FWD/REV dead time: The waiting and holding time before the motor changes its spinning direction after
the inverter's output frequency is decreased to zero. It is the time taken by the motor to change its spinning
direction when the inverter receives REV command during its running process. The time is shown in Figure
6-14:
Dead time
Reverse
Forward
Output frequency (
Hz)
Figure 6-14 FWD/REV dead time diagram
P8-13
Reverse control
Factory default
0
Setting range
0
Valid
1
Invalid
It is used to set if the inverter can run reverse, P8-13 is set to 1 for the applications that the motor can not
run reverse.
P8-14
Action when setting frequency lower
than frequency lower limit
Factory default
0
Setting range
0
Running at frequency lower limit
1
Stop
2
Zero speed running