KE300A Inverter Parameter Description
114
P7-03
Running status display 1
Factory default
1F
Setting
range
0000
~
FFFF
7
6
5
4
3
2
1
0
Running frequency(Hz)
Setting frequency(Hz)
DC bus voltage(V)
Output voltage(V)
Output current(A)
Output power(kW)
Output torque
DI input status
15 14 13 12 11 10 9
8
DO output status
AI1 voltage(V)
AI2 voltage(V)
Radiator temperature
Count value
Length value
Load speed display
PID setting
If the above parameters need to be displayed when
running, set the corresponding positions to 1, and change
the binary numbers into hexadecimal numbers, and then
enter them into P7-03.