KE300A Inverter Function Parameter List
68
Function
code
Name
Detailed instruction
Factory
default
Modify
selection when fault
1: Run at setting frequency
2: Run at upper limit frequency
3: Run at lower limit frequency
4: Run at abnormal backup frequency
P9-55
Abnormal backup
frequency
60.0% ~ 100.0% (100.0% corresponds
to maximum frequency( P0-10))
100.0%
○
P9-56
~
P9-58
Reserved
●
P9-59
Instantaneous power-off
action selection
0: Invalid
1: Deceleration
2: Dec-to-stop
0
○
P9-60
Recover judgment
voltage when
Instantaneous power-off
80 ~ 100.0%
90.0%
○
P9-61
Recover judgment time
when Instantaneous
power-off
0.00s ~ 100.00s
0.50s
○
P9-62
Action judgment voltage
when instantaneous
power-off
60.0% ~ 100.0% (standard bus
voltage)
80.0%
○
P9-63
Off-load protection
selection
0: Disable
1: Enable
0
○
P9-64
Off-load detection level
0.0 ~ 100.0
%
10.0%
○
P9-65
Off-load detection time
0.0 ~ 60.0s
1.0s
○
PA Group: PID Function
PA-00
PID given source
0: PA-01
1: AI1
2: AI2
3: Keypad potentiometer
4: High speed pulse HDI
5: Communication
6: Multi-step command
0
○
PA-01
PID given through
keypad
0.0 ~ PA-04 (PID given feedback
range)
0.0
○
PA-02
PID feedback source
0: AI1
1: AI2
2: Keypad potentiometer
3: AI1-AI2
4: High speed pulse HDI
5: Communication
0
○